Section: Perform Regular Maintenance
Perform Regular
Maintenance
Trained Service Technician's Regular
Maintenance
Annual Professional
Service Required
Tampering with or making incorrect
adjustments could lead to equipment
malfunction and result in asphyxiation,
explosion or fi re.
DO NOT TAMPER WITH THE UNIT OR CONTROLS
- CALL YOUR QUALIFIED SERVICE TECHNICIAN
OR SERVICEMAN.
To ensure continued reliable operation, a qualifi ed
service technician must service this burner annually.
More frequent service intervals may be required in
dusty or adverse environments.
Operation and adjustment of the burner requires
technical training and skillful use of combustion test
instruments and other test equipment.
Do Not Puncture, Scratch,
or Remove Flame Sighting
Windows
If a window is punctured, signifi cantly
scratched or removed from the throttle cup,
the burner performance could be impaired,
resulting in safety lockout, appliance soot-
up, equipment damage, hot gas puff-back
and asphyxiation hazard.
Use a clean soft cloth and degreaser, on an annual
basis, to remove any build-up or dark stains from the
windows.
If damaged, replace the nozzle line assembly with
an assembly that has a windowed throttle cup.
18
The following guidelines are provided for routine
maintenance.
Replace the oil supply line filter. The line
filter cartridge must be replaced to avoid
contamination of the fuel pump and nozzle.
Inspect the oil supply system. All fittings should
be tight and leak-free. The supply lines should
be free of water, sludge and other restrictions.
Remove and clean the pump strainer if
applicable.
Replace the used nozzle with a new nozzle
that conforms to the appliance manufacturer's
specifications.
Clean and inspect the electrodes for damage,
replacing any that are cracked or chipped.
Check electrode tip settings. Replace electrodes
if tips are rounded.
Inspect the igniter spring contacts.
Clean the cad cell lens surface, if necessary.
Make sure Low Firing Rate Baffle is in place
if required for the burner application. Omitting
the baffle can result in unacceptable burner
combustion.
Inspect all gaskets. Replace any that are
damaged or would fail to seal adequately.
Clean the blower wheel, air inlet, air guide,
retention head, throttle cup and throttle ring of
any lint or foreign material.
Use a clean soft cloth with a degreaser to
clean any accumulated soot or oil stains
from the throttle cup sight windows.
Check motor current. The amp draw should not
exceed the nameplate rating.
Check all wiring for secure connections or
insulation breaks.
Check the pump pressure and cutoff function.
Check primary control safety lockout timing.
Check ignition system for proper operation.
Inspect and clear the vent system and chimney
of any soot accumulation or other restriction.
Clean the appliance thoroughly according to the
manufacturer's recommendations.
Check the burner performance. Refer to the
section "Set combustion with test instruments".
It is good practice to keep a record of the service
performed and the combustion test results.