Beckett AFII85 Installation Manual page 9

Oil burner afii series types 'hlx' & 'fbx' air tube combinations voltage: 120 volts ac/60 hz
Table of Contents

Advertisement

Start
the
Burner
and Set Combustion
Figure
4. - Typical
Wiring,
R7184 Primary
Control
120
VAC BURNER
START WIRE
FROM
APPLIANCE
(FROM
LIMIT CIRCUIT)
. L1
2°VAC
l :
FROM
2
APPLIANCE
EQUIPMENT
GROUND
(HOT)
(NEUTRAL)
__GROUND S CREW
RED
BLACK
WHITE
WHITE
WHITE
WHITE
VIOLET
BLUE /
WHITE STRIPE
ORANGE
YELLOW
YELLOW
¢
¢
¢
¢
¢
¢
¢
¢
¢
¢
LIMIT
L1
L2
R7184
SERIES
PRIMARY
CONTROL
A
O_----
VALVE
AO i -
IGNITION
MOTOR
T 0"--"
CAD CELL
T 0"--"
CAD CELL
SK9359
TO REMOTE
LOW VOLTAGE
AC ALARM
_
CIRCUIT
(IF USED)
24
VAC
THERMOSTAT
BURNER
JUNCTION
BOX
....
=
120
VAC FIELD WIRING
120
VAC FACTORY WIRING
-
LOW VOLTAGE
FIELD WIRING
-
LOW VOLTAGE
FACTORY WIRING
/_
= WtRENUT
_
= WIRE WITH 1/4"
QUICK
CONNECT
RECEPTACLE
1. STANDBY. The burner is idle, waiting for a call for
heat. When a call for heat is initiated, there is a 3-
10 second delay while the control performs a safe
start check.
2, VALVE-ON
DELAY. The ignition and motor are
turned on for a 15 second valve-on delay.
3. TRIAL
FOR IGNITION
(TFI). The fuel valve is
opened. A flame should be established within the
15 second lockout time.
4. LOCKOUT.
If flame is not sensed by the end of
the TFI, the control shuts down on safety lockout
and must be manually reset. If the control locks out
three times in a row, the control enters restricted
lockout.
5. IGNITION
CARRYOVER.
Once flame is estab-
lished, the ignition remains on for 10 seconds to
ensure flame stability before turning off. If the con-
trol is wired for intermittent duty ignition, the ignition
unit stays on the entire time the motor is running.
6. RUN. The burner runs until the call for heat is sati-
fled. The burner is then sent to burner motor off
delay, if applicable, or it is shut down and sent to
standby.
Control System Features
Feature
Interrupted
Limited reset,
Diagnostic LED,
Valve-on
ignition
Limited recycle
cad cell indicator
delay
R7184A
YES
YES
YES
--
R7184B
YES
YES
YES
YES
R7184P
YES
YES
YES
YES
7. RECYCLE. If the flame is lost while the burner is
firing, the control shuts down the burner, enters a 60
second recycle delay, and then repeats the above
ignition sequence. If flame is lost three times in a
row, the control locks out to prevent cycling with
repetitious flame loss due to poor combustion.
8. BURNER
MOTOR-OFF
DELAY. The fuel valve
is closed and the burner motor is kept on for the
selected motor-off delay time before the control re-
turns the burner to standby.
P
STANOBY
RUN
Burner motor
off delay
YES
I
L_LOCKOUT
I
I
i
61351
Alarm Con-
tacts
Optional
RWB 6104 BAFII R01
Page 9