The T‐H2‐DV/T‐H2‐OS has a high‐temperature shut off switch built in as a standard safety feature (called 
a Hi‐Limit switch) therefore a "pressure only" relief valve is required. 
1.
This unit does not come with an approved pressure relief valve.  
2.
An approved pressure relief valve must be installed on the hot water outlet.  
3.
The pressure relief valve must conform to 
ANSI Z21.22 or CAN 1‐4.4 and installation 
must follow local code.  
4.
The  discharge  capacity  must  be  at 
least 199,000 BTU/h.  
5.
The  pressure  relief  valve  needs  to  be 
rated for a maximum of 150 psi. 
6.
The discharge piping for the pressure relief valve must 
be  directed  so  that  the  hot  water  cannot  splash  on 
anyone or on nearby equipment.  
7.
Attach  the  discharge  tube  to  the  pressure  relief  valve  and  run  the  end  of  the  tube  to  within  6" 
from  the  floor.  This  discharge  tube  must  allow  free  and  complete  drainage  without  any 
restrictions. 
8.
If the pressure relief valve installed on the T‐H2‐DV/T‐H2‐OS discharges periodically, this may be 
due to a defective thermal expansion tank or defective pressure relief valve.  
9.
The pressure relief valve must be manually operated periodically to check for correct operation.
• The T‐H2‐DV/T‐H2‐OS does not include a built‐in condensate neutralizer cartridge for reducing the 
pH level of condensate water.  If local codes dictate that condensate must be neutralized prior to 
drainage, a condensate neutralizer must be installed.  As an option, Takagi offers the TH‐NT01 
Neutralizer assembly (sold separately). 
• In the absence of applicable local codes and regulations, TAKAGI recommends that condensate be 
disposed of into a standard drain.  Connect a drain tube from the condensate drain port (shown 
below) located on the bottom of the T‐H2‐DV/T‐H2‐OS to a standard drain. 
 
 
 
• Follow  all  code  requirements 
of  the  local  authority  on 
condensate  neutralizers  and 
whether  or  not  they  are 
required for the installation.   
 
PRESSURE RELIEF VALVE 
CONDENSATE DRAIN 
20
As Close as
Possible
Pressure  
Relief Valve 
Condensate drain port 
 