Installation
Rear Vent Configuration Vented into Fireplace with Co-Linear Adapter
•
Attach the Co-Linear adapter directly to the back of the stove. Use two (2) 3" UL 441 or 1775 gas
liners to vent the appliance through a code-conforming masonry or metal (zc) fireplace. All
clearances to combustibles must be met and the flex vent must be vented through a non-
combustible fireplace chimney.
•
Use a high-wind termination cap.
•
Vent height must be a minimum 10' and maximum 25'.
•
Diffuser must be set to closed (#2) position.
•
Intake and exhaust restrictor must be set to the #1 (stock) position.
•
Do not install the intake damper plate or exhaust restrictor extender plates.
© Travis Industries
Min. 18"
4091120
(for qualified installers only)
High Wind Termination
46DVA-VCH
Liner Termination Kit
(Flashing and Adapter)
46DVA-GK
3" (77mm) Dia. Flex Lines
Co-Axial to Co-Linear Adapter
46DVA-TCL
21
100-01239_000