12.3

Electrical Specification

Nominal Capacity
AC Input rated Capacity*
Input Voltage
Input Frequency
Input power Factor
Current Harmonic Distortion
Input Capacity required*
Circuit breaker rating At 480 V Input
Nominal Capacity
DC Input Voltage window
recharge Voltage regulation
Nominal Capacity
AC output rated Capacity*
output Voltage
output power Factor
Voltage Distortion
Transient Voltage regulation
Transient Settling Time
Crest Factor
output Frequency
Synchronous window To Utility line
Frequency Slew rate
over load rating
G8000 Series with Isolated output Installation and operation manual
WARNING
DO NOT open the front cover.
electric shock, burns or other personal injuries may occur if
unqualified personnel open the front cover.
* Capacity: normal mode (recharge mode)
3% with 100% linear load / 5% with non-linear load
100% – Continuous / 125% – 10 min. / 150% – 1 min.
* Capacity: normal mode (recharge mode)
100 kW
110 kw (120 kw)
480 V ( +10% to -15% ), 3-phase 3-wire
60 Hz ±5%
1.00 – 0.95 lagging ( at 100% load )
5% maximum ( at 100% load )
111 kVA (124 kVA)
200 A
100 kW
288 – 414 V
± 1.5%
100 kW
100 kVA (100 kw)
208/120 V ± 1%, 3-Phase 4-Wire
1.0 pF: 32 – 86 °F (0 – 30 °C)
0.8 PF: 86 – 104 °F (30 – 40 °C)
< ± 2%
< 50 msec
2.0
60 Hz ± 0.01% ( at Free-running Mode)
59 Hz – 61 Hz
1 Hz/Sec
150 kW
165 kW (180 kW)
166 kVA (184 kVA)
300 A
150 kW
150 kW
150 kVA (150 kw)