Anchor Bolts - Toshiba G8000 SERIES Installation And Operation Manual

480/208 v 100/150 kw
Hide thumbs Also See for G8000 SERIES:
Table of Contents

Advertisement

10.3

Anchor Bolts

Install the anchor bolts to secure the UPS on the floor. See Figure 10.2 for anchor bolt installation detail.
Use 12mm (1/2") diameter anchor bolts. There are 16mm (5/8") diameter holes provided in the UPS base.
See Figure 10.3 for the hole locations and dimensions for the specified UPS models.
4 x 5/16 in. (16 mm)
diameter screw holes
Anchor Bolt
FIGURE 10.2
ANCHOR BOLT INSTALLATION DETAIL
28
4 screw holes
(Side View)
G8000 Series with Isolated output Installation and operation manual
100 kVA
Back
4 X 1/2 in. Dia. (12 mm)
Front
29 11/16 in. (754 mm)
150 kVA
Back
4 X 1/2 in. Dia. (12 mm)
Front
46 1/16 in. (1170 mm)
FIGURE 10.3
HOLE LOCATIONS/DIMENSIONS
ON BOTTOM OF UPS
21 11/16 in.
(551 mm)
21 11/16 in.
(551 mm)