Factory Authorized Personnel; Important Safety Instructions - Toshiba G8000 SERIES Installation And Operation Manual

480/208 v 100/150 kw
Hide thumbs Also See for G8000 SERIES:
Table of Contents

Advertisement

be trained and authorized to safely energize, de-energize, ground, lockout/tagout circuits and equipment, and clear
faults in accordance with established safety practices.
be trained in the proper care and use of protective equipment such as safety shoes, rubber gloves, hard hats, safety
glasses, face shields, flash clothing, etc., in accordance with established safety practices.
Be trained in rendering first aid.
For further information on workplace safety visit www.osha.gov.
2.4

Factory Authorized Personnel

Factory authorized personnel have been factory trained and certified to install, service, and repair the UPS. Contact the
Toshiba Customer Support Center for assistance in locating the factory authorized personnel nearest you.
3

Important Safety Instructions

The following contains important instructions that should be followed during the installation, operation, and maintenance of
the G8000 Series UpS.
please refer to the battery manufacturer's instructions for details on operating, maintaining and/or replacing the batteries
for each system. Unauthorized personnel from batteries. only a factory authorized representative with battery experience
should perform service on batteries.
misuse of this equipment could result in personal injury and/or equipment damage.
In no event will Toshiba Corporation be responsible or liable for either indirect or
consequential damage or injury that may come from the use of this equipment.
The UPS system input and output is NOT equipped with an over-current protection device, or an output disconnection
at the AC output. The user should provide circuit breakers between the UpS AC input (or bypass input) and the power
sources and between the UpS output and the critical load input. The minimum device ratings are listed in Table 3.1.
C
100 kVA
150 kVA
The maximum operating ambient temperature is 86 °F (30 °C) at 1.0 PF, and 104 °F (40 °C) at 0.8 PF. If the UPS is exposed
to the same ambient temperature as the battery system, the maximum operating ambient temperature should be 86 °F (30
°C) at 1.0 PF, 90 °F (32 °C) at 0.8 PF. Table 3.2 lists the nominal battery voltage.
4
TABLE 3.1 UPS MINIMUM DEVICE RATINGS
R
O
apaCity
ated
utput
208/120 V
208/120 V
TABLE 3.2 UPS NOMINAL BATTERY VOLTAGE
C
apaCity
100 kVA
150 kVA
CAUTION
i
B
R
nput
ReakeR
ating
480 V-200 A
480 V-300 A
n
V
F
Ominal
Oltage
lOat
360 Vdc
405 V
360 Vdc
405 V
G8000 Series with Isolated output Installation and operation manual
O
B
R
utput
ReakeR
ating
208 V-350 A
208 V-600 A
V
Oltage