Messages List - GE 400 User Manual

Sg series 400 & 500 kva / 480vac ul / s2
Hide thumbs Also See for 400:
Table of Contents

Advertisement

6.3.3 Messages list

Code
Message
4002
WATCHDOG RESET
4108
Q4 OPEN
4108
Q4 CLOSED
4111
RECTIFIER UTILITY OK
4119
BATTERY TEST STARTED
4120
BATTERY TEST STOPPED
4122
MANUAL BOOST CHARGE ON
AUTOMATIC BOOST CHARGE
4123
4124
BOOST CHARGE OFF
4161
RECTIFIER ON
4162
RECTIFIER OFF
4163
GENERATOR ON
4164
GENERATOR OFF
INVERTER CANNOT BE TURNED
4302
INVERTER CANNOT BE TURNED
4303
4361
INVERTER ON
4362
INVERTER OFF
4411
BYPASS UTILITY OK
4500
COMMAND LOAD OFF
4521
NO BYPASS POWER
Modifications reserved
OPM_SGS_USM_M40_M50_2US_V010.doc
The microprocessor has detected an incorrect operation:
Transfers the Load on Utility and performs a program
reset.
The Inverter will restart automatically and will supply the
Load.
The auxiliary contact indicates that the input rectifier
switch Q4 has been opened.
The auxiliary contact indicates that the input rectifier
switch Q4 has been closed.
Rectifier Input Utility is again within the admitted tolerance
(voltage, frequency and phase).
Start of Manual or Automatic Battery Test.
End of Manual or Automatic Battery Test.
Start of Manual Boost charge (only for lead open wet
batteries).
Start of Automatic Boost charge (only for lead open wet
ON
batteries).
End of Manual or Automatic Boost charge (only for lead
open wet batteries).
Rectifier started.
Rectifier shutdown.
Customer Interface Board (X1 - 11, 22) received a Gen-set
ON signal.
Operating mode depend on setting of Parameters.
Customer Interface Board (X1 - 11, 22) received a Gen-set
OFF signal.
Function Bypass enabled depends on setting of parameter.
Inverter cannot be switched on because one of the
following conditions is still present:
- Over Temperature
ON
- Low Battery Voltage
- Inverter Fuses
- Overload
Inverter cannot be switched OFF, because the Load cannot
be switched to Utility (voltage out of tolerance, not
OFF
synchrony, BP blocked).
The command to start the Inverter has been activated on
the control panel.
The command to switch OFF the Inverter has been
activated by the control panel or automatically for alarm
presence.
Bypass Input Utility is again within tolerance (voltage,
frequency and phase).
Disconnection of the Load by opening K6 and K7 for:
EPO / Load Off / Overload / Stop Operation.
With the Load supplied by Automatic Bypass, a Utility
Failure or K6 opening occurred.
Meaning
- K7 opening Failure
- High Battery Voltage
- DC Low
- EPO
User Manual SG Series 400 & 500 UL S2