GE 400 User Manual page 66

Sg series 400 & 500 kva / 480vac ul / s2
Hide thumbs Also See for 400:
Table of Contents

Advertisement

3. Perform the command "Load Off" on the Unit to
separate only when the LED 7 (Q1 closed) is Off.
Perform the command "Load Off" by entering the screen
(see Section 7.5):
COMMANDS / REQUEST TOTAL OFF
Synoptic Diagram of the unit to separate
4. Disconnect the Battery on the Unit to separate by opening (Pos. O) the External Battery Switch
or Fuses.
• Wait 5 minutes for DC-Link Capacitors discharge.
5. Disconnect the Utility supply on the Unit to separate.
Complete power shutdown will OFF the LCD Display Panel.
Synoptic Diagram of the unit to separate
DANGER !
It will take 5 minutes for the DC capacitors to discharge.
Open only the front door, do not open any other part of the UPS.
NOTE !
For any further intervention contact nearest Service Center.
Modifications reserved
OPM_SGS_USM_M40_M50_2US_V010.doc
END OF PROCEDURE
Home\Commands
COMMANDS
RESET TOTAL OFF
REQUEST TOTAL OFF
Synoptic Diagram of other units
Synoptic Diagram of other units
User Manual SG Series 400 & 500 UL S2
Page 66/79