Example 5:
An equivalent set of parameters for Example 4 is.
Weekday
d1
- Saturday
eBoost START
00:00
eBoost STOP
23:59
eBoost START
eBoost STOP
The eBoost™ Operation Mode is active from 18:00 of weekday d3 - Monday until 06:00 of weekday d4 -
Tuesday (as indicated by the eBoost STOP time of weekday d4 - Tuesday).
The eBoost STOP time of weekday d3 - Monday has no effect as it is followed by the eBoost STOP time
of weekday d4 - Tuesday.
It can be, without change of meaning, any time between 18:00 and 23:59.
Similarly, the eBoost™ Operation Mode is active from 18:00 of weekday d4 - Tuesday until 06:00 of
weekday d5 - Wednesday.
The eBoost START time of weekday d5 - Wednesday has no effect as it is preceded by the eBoost START
time of weekday d4 - Tuesday.
It can be, without change of meaning, any time between 00:00 and 06:00.
NOTE !
To avoid undesired eBoost™ Operation Mode, verify:
• Date and Time (first page of parameter).
• eBoost™ screen how many hours of eBoost™ Operation Mode have been selected
for each day of the week.
NOTE !
The eBoost™ Operation Mode will become active only if the Load is supplied from
the Inverter.
Modifications reserved
OPM_SGS_USM_M40_M50_2US_V010.doc
d2
d3
- Sunday
- Monday
00:00
18:00
20:00
18:00
d4
d5
- Tuesday
- Wednesday
18:00
06:00
06:00
06:00
d6
d7
- Thursday
- Friday
09:00
12:00
09:00
13:00
Page 42/79
User Manual SG Series 400 & 500 UL S2