GE 400 User Manual page 22

Sg series 400 & 500 kva / 480vac ul / s2
Hide thumbs Also See for 400:
Table of Contents

Advertisement

LED Stop Operation (red color)
It warns about the imminent inverter stop (default parameter = 3 min.) and the
consequent load shutdown as result of:
LED Alarm (yellow color)
It blinks when one or more alarm is activated. The internal buzzer is ON.
The LED remains lighted (with the alarm condition still present) and the buzzer
stops when the key "MUTE" is pressed.
The LED is also lit when the load is not protected by UPS or in case Q1 is open.
LED Operation (green color)
When lit, indicates that the UPS is functioning correctly and the load is system
protected (Load supplied from inverter).
When blinking, indicates that a regular maintenance service is needed (SERVICE
REQUIRED).
May be reset by a service technician only.
See Section 9 – Maintenance – Service check.
The LED is OFF when the output switch Q1 is open, indicating that the Inverter is in
service mode, not supplying the load.
Modifications reserved
OPM_SGS_USM_M40_M50_2US_V010.doc
The battery is fully discharged and the load cannot be transferred on utility.
Overtemperature or overload condition (>125%) and the load cannot be
transferred on utility.
User LCD Interface
The user interface consists of a Back lit Graphic
Display (LCD) having:
Synoptic Diagram indicating UPS status.
UPS
operating,
information.
History of events (alarms and messages).
Functionality can be programmed to meet
customer needs by changing parameters.
Operation commands of the UPS.
AC
and
DC
metering
Page 22/79
User Manual SG Series 400 & 500 UL S2