Precharged Line Routing - Remote Only

Do not connect the precharged tubing until all
routing and forming of the tubing is complete. See
the Coupling Instructions for final connections.
1. Each set of pre-charged tubing lines contains a
3/8" diameter liquid line, and a 1/2" diameter
discharge line. Both ends of each line have quick
connect couplings.
Note: The openings in the building ceiling or wall,
listed in the next step, are the minimum sizes
recommended for passing the refrigerant lines
through.
2. Have the roofing contractor cut a minimum hole
for the refrigerant lines of 2". Check local codes, a
separate hole may be required for the electrical
power supply to the condenser.
Potable Water
Supply
To Remote
Fan Motor
Condenser
Condensate
Drain
July 2009
Page 12
Caution: Do NOT kink the refrigerant tubing while
routing it.
3. Route the refrigerant tubes thru the roof opening.
Follow straight line routing whenever possible.
Excess tubing may EITHER be coiled up INSIDE
the building OR cut out prior to connection to the
ice maker and condenser.
If the excess tubing is cut out, after re-brazing the
tubing must be evacuated prior to connection to the
ice maker or condenser.
If the excess tubing is to be coiled, spiral it
horizontally to avoid excess trapping in the lines.
5. Have the roofing contractor seal the holes in the
roof per local codes
Power Supply
to Condenser
Pre-Charged
Tubing Line
Set