Precharged Line Routing - Scotsman C0530SR-1 Technical Manual

Table of Contents

Advertisement

General Installation - Remote

Precharged Line Routing

Do not connect the precharged tubing until all routing and forming of the tubing is complete.
See the Coupling Instructions for final connections.
1. Each set of pre-charged tubing lines contains a 3/8" diameter liquid line, and a 1/2" diameter
discharge line. Both ends of each line have quick connect couplings, the end without access
valves goes to the ice maker.
Note: The openings in the building ceiling or wall, listed in the next step, are the minimum sizes
recommended for passing the refrigerant lines through.
2. Have the roofing contractor cut a minimum hole for the refrigerant lines of 1 3/4". Check
local codes, a separate hole may be required for the electrical power supply to the condenser.
Caution: Do NOT kink the refrigerant tubing while routing it.
3. Route the refrigerant tubes thru the roof opening. Follow straight line routing whenever
possible. Excess tubing may EITHER be coiled up INSIDE the building OR cut out prior to
connection to the ice maker and condenser.
If the excess tubing is cut out, after re-brazing the tubing must be evacuated prior to
connection to the ice maker or condenser.
Note brazing requires a nitrogen purge.
If the excess tubing is to be coiled, spiral it horizontally to avoid excess trapping in the lines.
5. Have the roofing contractor seal the holes in the roof per local codes
September 2006 Page 15

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents