Wireless Installation; Wireless Menu - Baxi Ecogen 24/1.0 Installation & Servicing Instructions Manual

Gas fired wall mounted condensing boiler and power generator
Table of Contents

Advertisement

NOTE: The THINK Controller refresh rate will be slower than when it is
mounted directly on the appliance or in a wired cradle.
IMPORTANT: Before running the appliance ensure parameter 5700 has
been set according to the type of system installed. See sections 10.4 to 10.11
for system types and section 11.3.k for the change procedure.

Wireless menu

Line 2
1.
Binding
2.
Test mode
3.
Room Unit 1
4.
Room Unit 2
5.
Room Unit 3
6.
Outside sensor
7.
Repeater unit
8.
Operator Unit 1
9.
Delete all devices
50
© Baxi Heating UK Ltd 2012
Line 3
Trigger?
no/yes
Trigger?
no/yes
Delete device?
missing/in operation
Delete device?
missing/in operation
Delete device?
missing/in operation
Delete device?
missing/in operation
Delete device?
missing/in operation
Delete device?
missing/in operation
-
no/yes
10.0 Electrical
10.17

Wireless Installation

1. If a wireless system is being installed then communication
must be establish between the various RF components and the
special RF 5 LED Receiver which contains the transceiver for
the appliance. Each kit as outlined in section 6.8 includes
installation instructions. An overview is given below: -
2. In the wireless 5 LED kit (part no. 720026201) the wireless 5
LED Receiver and the cradle are prebound but subsequent
cradles holding THINK Controller for second heating circuits
must be connected or 'bound' to the 5 LED transceiver.
3. The available RF component transmitters are: -
• The cradle – enables direct connection with the THINK
Controller.
• The outside sensor transmitter.
• The repeater unit – enables components to be positioned in
otherwise dead areas to the RF 5 LED Receiver. The repeater
unit requires a mains supply.
4. Observe the same considerations for locating the wireless
THINK Controller as the wired room sensor.
5. To bind the units together use the following procedures.
6. Each THINK Controller must be allocated to the correct heat
circuit i.e. room unit 1/room unit 2/operator unit as described in
Section 10.13 and 11.3 paragraph k, this can be done on the
appliance or later when in the RF cradle.
7. Switch the appliance on and insert the RF 5 LED Receiver
into either the appliance or an off appliance wired cradle.
8. If the RF Cradle and RF 5LED Receiver came boxed together
then they will be prebound. Insert the 3xAA batteries into the
RF cradle and insert the THINK Controller, 'data update' will
show and then the percentage progress will show if the
THINK Controller is new to the appliance. After a short while
'Operator unit ready' then the standard screen will appear. The
THINK Controller can now be used as an RF programmable
room sensor.
9. If Error 83 appears move the THINK Controller in the RF
cradle closer to the RF 5 LED Receiver. If distance/line of sight is
not the problem the RF components will need to be connected
or 'bound' together using the following procedure: -
Parameter
10. Press and hold the reset button on the RF 5 LED Receiver
120
around 10 seconds until the second and fourth LEDS are lit.
121
130
11. Press the menu button to enter the user menu and then
131
press and hold the easy menu and menu buttons untill the
other access levels appear. Scroll down to the commissioning
132
option and select by pressing the Selector Button. Scroll down
133
to the wireless options and select to enter this list as shown
134
opposite.
135
140
12. Select parameter 120, scroll to 'yes'. 'Wait' will appear until
the unit is bound. As each unit is bound they will appear in the
list above as being 'in operation'. If a unit does not appear, move
it to a different location and then choose and confirm test
mode. This will initiate a series of 24 test signals which are
shown along the top of the display and sent back and shown on
a line underneath. Move the unit to a location where at least 20
of these signals are echoed back. If few or no signals are
received it will be necessary to use a repeater unit to relay the
signal.