A vent damper is provided to allow fine tuning
of the draft. Too little draft will cause flames to be too
long with black tips and too much draft will cause
flames to be short and blue.
To adjust the damper, burn the unit on High 0
minutes or more. Adjust the vent damper to a posi-
tion in the ranges listed below that produces the most
desirable flame pattern.
range Of Approved Damper Settings
Natural Gas or Propane
0 Feet (rear vent)
6 feet
12 feet
24 feet
36 feet
vENTING
Damper Settings
Top Vent Only
Open
1/4 to Open
1/4 to Open
Closed to 1/2
Closed to 1/2
Vent damper shown in the
Maximum Draft"OPEN" position
for top vent. Note: This would be
the Minimum Draft"CLOSED"
position if a rear vent was
installed.
Only For Qualified Installers
CLOSED