LG ARNH963K2A2 Installation Manual page 69

Hydro kit medium temperature (k2) btu/h 107,500; hydro kit high temperature (k3) btu/h 86,000
Hide thumbs Also See for ARNH963K2A2:
Table of Contents

Advertisement

temperature control Parameter setting for Hydro Kit High temperature -
continued
function Codes 2E and 2f
Changing Thermal ON/OFF temperature and temperature gap. Refer to Table 19 and Table 20 for the two types of thermal temperature values.
Table 19: Room Air Temperature
Thermal on
0
-0.9°F (-0.5°C)
1
7.2°F (4°C)
2
3.6°F (2°C)
3
-1.8°F (-1°C)
function Code 30
Displays Remote Controller Program Version when selected.
Thermal off
2.7°F (1.5°C)
10.8°F (6°C)
7.2°F (4°C)
1.8°F (1°C)
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG Life's Good" is a registered trademark of LG Corp.
Pre-coMMIssIoNING
Function Codes - Hydro Kit High Temperature
Table 20: Leaving Water Temperature and Indirect Storage
Tank Temperature
Thermal on
0
-3.6°F (-2°C)
1
-10.8°F (-6°C)
2
-3.6°F (-2°C)
3
-1.8°F (-1°C)
Thermal off
3.6°F (2°C)
7.2°F (4°C)
7.2°F (4°C)
1.8°F (1°C)