Fluke 1730/BASIC User Manual page 55

Energy logger
Hide thumbs Also See for 1730/BASIC:
Table of Contents

Advertisement

Total Harmonic Distortion (THD) ........................ THD for voltage and current is calculated on 25 harmonics
Averaging Time .................................................. User selectable: 1 sec, 5 sec, 10 sec, 1 min, 5 min, 10 min, 15 min, 30 min
Demand Interval ................................................. User selectable: 5 min, 10 min, 15 min, 20 min, 30 min
Data Storage ...................................................... Internal flash memory (not user replaceable)
Memory Size ....................................................... Typical 20 logging sessions of 10 weeks with 10-minute intervals
Shop for Fluke products online at:
Logging Period
Averaging Period
Recommended for
20 sessions
1 sec
3 hr
5 sec
15 hr
10 sec
28 hr
30 sec
3.5 days
1 min
7 days
5 min
5 weeks
10 min
10 weeks
15 min
3.5 months
30 min
7 months
[1] The number of possible logging sessions and logging period depends on user requirements.
MyFlukeStore
www.
[1]
Logging Period for
1 session
2.5 days
12 days
24 days
10 weeks
20 weeks
2 years
>2 years