White Rodgers 1F60-22 Installation & Operating Manual page 14

Setback thermostat
Table of Contents

Advertisement

CAUTION
If the outside temperature is
below 40 F, OMIT STEP 3.
Running the air conditioner
when the temperature is below
40 F can damage the compres-
sor.
3. (For heat/cool systems only). Move
the system switch to Cool. Move the
temperature-set switch until it is set
to a temperature that is approxi-
mately 5 F below the displayed room
temperature. The air conditioner
should come on within two minutes.
Move the temperature-set switch at
14
least 5 F above the displayed room
temperature. The air conditioner
should shut off within two minutes.
4. Move the system switch to Heat.
Move the temperature-set switch
until it is set to a temperature that is
approximately 5 F above the dis-
played room temperature. The
furnace should come on within two
minutes. Move the temperature-set
switch at least 5 F below the dis-
played room temperature. The
furnace should turn off within two
minutes (although the fan may
continue to run for several more
minutes).