Download Print this page

AEG Protect 3.M 2.0 Manual page 3

Uninterruptible power supply 3-phase input; 3-phase output, 20–120 kva power supply
Hide thumbs Also See for Protect 3.M 2.0:

Advertisement

Classification VFI SS 111 acc. to IEC 62040-3
Power type rating
SyStEM
Nominal input current
Efficiency (typical)
Efficiency in ECO mode
Waste heat from power (typical)
Airflow (max.) m³/h
INPut
Nominal voltage
Input voltage range
Frequency
total harmonic distortion (tHDv)
Power factor
INVErtEr
Nominal voltage
Frequency
Precision static /dynamic
total harmonic distortion (tHDv)
Max. phase displacement
Admissible overload
Crest factor
Max. short circuit current
Admissible power factor
BAttEry
rated voltage
Max. charging power
Charging principle
Autonomy time
StAtIC ByPASS
Nominal voltage
Frequency
Synchronization range
transfer time at mains outage
Admissible overload
GENErAl DAtA
Parallel mode
Audible noise
Operating temperature range / humidity
Protection
Color
Cable entry
Environmental conditions
COMMuNICAtION
Display
Alarm signals
Interfaces
DIMENSIONS
Dimensions approx. D x W x H (mm)
Footprint (m²)
Weight approx.
Weight approx. (incl. module)
1) by THDv ≤2 %
20 kVA
40 kVA
16 kW
32 kW
29 A
59 A
1.3 kW
2.6 kW
4436 BTU/h
8872 BTU/h
309
617
3 x 400 V (380 V, 415 V adjustable), 3 phase + neutral
3 x 400 V (380 V, 415 V adjustable), 3 phase + neutral
<3 % ( linear load), <5 % (non-linear load)
±1.5 % (balanced load), ±2 % (100 % unbalanced load)
5 A
10 A
Load switching per power module
Selectable over external battery cabinet
3 x 400 V (380, 415 V adjustable), 3 phase + neutral
Up to 4 UPS (central battery possible)
62 – 69 dB(A) dependent on equipment installed and load state
0 – 40 °C / <95 % (without condensation)
Free from corrosive air and conductive dust
Remote signal contact, RS232, 2 x communication slots for SNMP / Modbus / additional relay cards
910 x 520 x 1165
0.47
139 kg
169 kg
199 kg
Protect 3.M 2.0
60 kVA
80 kVA
48 kW
64 kW
88 A
117 A
95 %
98 %
3.9 kW
5.2 kW
13308 BTU/h
17744 BTU/h
926
1234
305 – 477 V
50 Hz/ 60 Hz (adjustable)
≤3 %
1)
>0.99
50 / 60 Hz (adjustable)
±1 % / ±7 %
125 % for 10 min., 150 % for 60 s
2.7 : 1
>270 % of the rated current
0.1 inductive to 0.1 capacitive
±240 V DC
15 A
20 A
50 Hz / 60 Hz (adjustable)
±0.1 – ±5 % (adjustable)
0 ms (without interruption)
175 % for 10 ms
IP20
RAL 7035
Underside
320 x 240 graphical LCD display
Acoustic and visual
229 kg
259 kg
100 kVA
120 kVA
80 kW
96 kW
145 A
172 A
6.5 kW
7.8 kW
22180 BTU/h
26616 BTU/h
1543
1852
25 A
30 A
975 x 520 x 1655
0.51
204 kg
354 kg
384 kg
3

Advertisement