System Status Points - GE D400 Hardware User Manual

Substation gateway
Hide thumbs Also See for D400:
Table of Contents

Advertisement

CHAPTER 7: USING THE D400

System status points

D400 SUBSTATION GATEWAY USER'S MANUAL
You can obtain status information about your D400 through several system points. These
points can be viewed through the Application tab on the Point Summary window.
Table 23: D400 System Status Points
Name
Data Type
Power Supply 1 Good
Digital Input
Power Supply 2 Good
Digital Input
IRIG-B Enabled
Digital Input
IRIG-B Watchdog Expired Digital Input
Front Port Link Good
Digital Input
NET1 Port 1 Link Good
Digital Input
NET1 Port 1 Active
Digital Input
NET1 Port 2 Link Good
Digital Input
NET1 Port 2 Active
Digital Input
NET1 Port 3 Link Good
Digital Input
NET1 Port 3 Active
Digital Input
NET1 Port 4 Link Good
Digital Input
NET1 Port 4 Active
Digital Input
NET2 Port 1 Link Good
Digital Input
NET2 Port 1 Active
Digital Input
NET2 Port 2 Link Good
Digital Input
NET2 Port 2 Active
Digital Input
NET2 Port 3 Link Good
Digital Input
NET2 Port 3 Active
Digital Input
NET2 Port 4 Link Good
Digital Input
NET2 Port 4 Active
Digital Input
System PLD Revision
Analog Input
Main Board ID
Analog Input
Mid-Plane ID
Analog Input
NET1 Card ID
Analog Input
NET2 Card ID
Analog Input
USB KVM Card ID
Analog Input
FPGA Version 1.10 or above is required to provide system status points for the power
supplies and 100BASE-FX card. In previous FPGA versions, these points appear as offline
regardless of their actual status. If your FPGA version is 1.09 or less, please contact Product
Support.
Description
Value is 1 when a failure has occurred or the power
supply is not installed. Because this point remains
online even when the power supply is not installed, you
can force the point for the missing supply to the offline
state or you can apply a tag indicating that the unit is
not installed.
Value is 1 when enabled
Value is 1 when expired
Value is 1 when true
Note that "Active" is not the same as "Activity". It is used
in the same sense as Active and Standby for redundant
Ethernet configurations. The point does not flicker on
and off in the same way that the activity LED does for
an Ethernet port.
The actual number of ports available depend on the
configured options of the D400 unit. Points associated
with unavailable ports are made offline and invalid.
A string that describes the revision or ID number of the
specified component.
GENERAL
SYSTEM STATUS POINTS
97

Advertisement

Table of Contents
loading

Table of Contents