CHAPTER 5: POWERING UP THE D400

Power supply alarms

D400 SUBSTATION GATEWAY USER'S MANUAL
Power Source
Connection
Two External DC
First source connected
Power Sources
to SUPPLY1 terminals.
with Optional
Second source
Redundant D400
connected to SUPPLY2
DC Power
terminals.
Converter
3.
Connect protective earth wire to the Protective Earth terminal
The terminal is an M5 threaded stud with M5 nut and washers. The recommended
order for stacking the washers on the chassis is: flat washer, ground wire ring terminal,
toothed washer, M5 nut.
For proper transient protection, the recommended tool torque settings for the M5 nut
is 18.1 in-lb [2.04 Nm].
It is recommended to terminate 12 AWG green & yellow wire with a Panduit PV10-14R
or equivalent ring terminal.
4.
Verify that Power LEDs on the front panel of the power supplies and the D400 main
module are lit.
5.
Replace the terminal block protective plastic cover.
The D400 includes connections for two alarm outputs:
Power Fail to indicate one of the two power supplies or one of the two power feeds
has failed
System Fail to indicate system operation status
Terminal block TB2 on the rear panel of the D400 provides contact closure outputs for
connection to an external circuit, for example, to connect an external LED indicator or
audible alarm.
The contact closure used for alarm outputs is a solid-state photo-MOS device. Contact
closure output ratings at maximum ambient temperature are:
Continuous current: 0.1 A continuous at 300 VAC / 300 VDC
Peak current: 0.28 A peak for 10 ms
Maximum on resistance: 35 ohm
Dielectric isolation: 2 kV
Wiring Diagram
DC Power Source #1
RMS
GENERAL
POWER SUPPLY ALARMS
Supply 1
Supply 2
+
-
+
DC Power Source #2
-
on the rear panel.