Requirements For The; Commonwealth Of Massachusetts; New York City Approval - Lennox EDVSTNM-B Installation Instructions Manual

Elite series edv direct-vent gas fireplaces
Table of Contents

Advertisement

Gas Pressure - All Models
Tables 2 and 3 show the appliances' inlet and
manifold gas pressure requirements:
Inlet Gas Supply Pressure
(all models)
Fuel #
Minimum
4.5" WC
Natural Gas
(1.12 kPa)
11.0" WC
Propane
(2.74 kPa)
Table 2
Manifold Gas Supply Pressure
(all models)
Fuel #
Low
Natural
(Lo) 2.2" WC
Gas
(0.55 kPa)
(Lo) 6.3" WC
Propane
(1.57 kPa)
Table 3
Test gauge connections are provided on the
front of the millivolt and electronic gas control
valve (identified IN for the inlet and OUT for the
manifold side). The control valves have a 3/8"
(10mm) NPT thread inlet and outlet side of the
valve (refer to Figures 1 and 2).
Propane tanks are at pressures that will cause
damage to valve components. Verify that the
tanks have step down regulators to reduce the
pressure to safe levels.
These appliances must be isolated from the
gas supply piping system (by closing their
individual manual shut-off valve) during any
pressure testing of the gas supply piping
system at test pressures equal to or less
than 1/2 psig (3.5 kPa).
These appliances and their individual shut-off
valves must be disconnected from the gas
supply piping system during any pressure
testing of that system at pressures greater
than 1/2 psig (3.5 kPa).
These appliances must not be connected to a
chimney or flue serving a separate solid fuel
burning appliance.
4
Orifice Sizes - Sea Level to High Altitude
(All Models)
These appliances are tested and approved for
installation at elevations of 0-4500 feet (0-1372
meters) above sea level using the standard burner
orifice sizes (marked with an "*" in Table 4 ).
Maximum
For elevations above 4500 feet, contact your gas
supplier or qualified service technician.
10.5" WC
(2.61 kPa)
Deration - At higher elevations, the amount
13.0" WC
of BTU fuel value delivered must be reduced
(3.23 kPa)
by either:
• Using gas that has been derated by the gas
company.
• By changing the burner orifice to a smaller
size as regulated by the local authorities having
jurisdiction and by the (USA) National Fuel Gas
Code NFPA 54/ANSI Z223.1 - latest edition or,
High
in Canada, the CAN/CSA-B149.1 codes - latest
(Hi) 3.5" WC
edition.
(0.87 kPa)
Install the appliance according to the regulations
(Hi) 10.0" WC
of the local authorities having jurisdiction and,
(2.49 kPa)
in the USA, the National Fuel Gas Code NFPA
54 / ANSI Z223.1 - latest edition or, in Canada,
the CAN/CSA-B149.1 - latest edition.
Flame breadth, height and width will diminish
4% for every 1,000 feet of altitude.
Burner Orifice Sizes (all models)
Elevation
Feet (meters)
0-4500
(0-1372)
Table 4
Gas Valve Diagrams
See Figure 1 for Millivolt models and Figure 2
For Electronic Models.
Main Gas Control Knob
IN
Manifold Pressure Tap
Inlet Pressure Tap
Figure 1 -
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Natural
Propane
Gas
Gas
drill size (inches)
drill size (inches)
(0.125")
*
#41 (0.096")
*
21L81 •
21L82 •
* Standard size installed at factory
• Part /Cat. Number
Pilot Adjustment
Screw
OFF/PILOT/ON
OUT
HI/LO Variable
Flame Height
Adjustment
SIT Millivolt Gas Valve
Honeywell Electronic
Figure 2
REQUIREMENTS FOR THE COMMON-
WEALTH OF MASSACHUSETTS
These fireplaces are approved for installation in
the US state of Massachusetts if the following
additional requirements are met:
• Install this appliance in accordance with
Massachusetts Rules and Regulations 248
C.M.R.
• Installation and repair must be done by a
plumber or gas fitter licensed in the Com-
monwealth of Massachusetts.
• The flexible gas line connector used shall
not exceed 36 inches (92 centimeters) in
length.
• The individual manual shut-off must be a
T-handle type valve.
Massachusetts Horizontal Vent Requirements
In the Commonwealth of Massachusetts, hori-
zontal terminations installed less than seven
(7) feet above the finished grade must comply
with the following additional requirements:
• A hard wired carbon monoxide detector
with an alarm and battery back-up must be
installed on the floor level where the gas
fireplace is installed. The carbon monoxide
detector must comply with NFPA 720, be
ANSI/UL 2034 listed and be ISA certified.
• A metal or plastic identification plate must
be permanently mounted to the exterior of
the building at a minimum height of eight (8)
feet above grade and be directly in line with
the horizontal termination. The sign must
read, in print size no less than one-half (1/2)
inch in size, GAS VENT DIRECTLY BELOW.
KEEP CLEAR OF ALL OBSTRUCTIONS.
NEW YORK CITY, NEW YORK (MEA)
Installation of these fireplaces are approved
for installation in New York City in the US state
of New York.
Gas Valve