Gas Pressure Requirements; Orifice Sizes; Gas Valve Diagrams; Requirements For The Commonwealth - Lennox MLBV-35NM Installation Instructions Manual

B-vent merit series
Table of Contents

Advertisement

LENNOX HEARTH PRODUCTS • MERIT

GAS PRESSURE REqUIREMENTS

(All Models)
Tables 2 and 3 show the appliances' inlet and
manifold gas pressure requirements:
Inlet Gas Supply Pressure
(All models)
fuel #
Minimum
4.5" WC
Natural Gas
(1.12 kPa)
11.0" WC
Propane
(2.74 kPa)
Table 2
Manifold Gas Supply Pressure
(All models)
fuel #
Low
Natural
(Lo) 2.2" WC
Gas
(0.55 kPa)
(Lo) 6.3" WC
Propane
(1.57 kPa)
Table 3
Test gauge connections are provided on the
front of the gas control valve, identified IN for
the inlet and OUT for the manifold side (see
Figures 1 and 2).
Propane tanks are at pressures that will cause
damage to valve components. Verify that the
tanks have step-down regulators to reduce the
pressure to safe levels.
These appliances must be isolated
from the gas supply piping system (by
closing their individual manual shut-off
valve) during any pressure testing of
the gas supply piping system at test
pressures equal to or less than 1/2 psig
(3.5 kPa).
These appliances and their individual
shut-off valves must be disconnected
from the gas supply piping system
during any pressure testing of that
system at pressures greater than 1/2
psig (3.5 kPa).
4
SERIES B-VENT GAS FIREPLACES • MODELS MLBV-35, MLBV-40 • INSTALLATION INSTRUCTIONS
®

ORIfICE SIzES

Sea Level to High Altitude
(All Models)
These appliances are tested and approved for
installation at elevations of 0–4500 feet (0–1372
meters) above sea level using the standard
burner orifice sizes (marked with an asterisk
(*) in Table 4, below).
Maximum
For elevations above 4500 feet, contact your
10.5" WC
gas supplier or a qualified service technician.
(2.61 kPa)
13.0" WC
deration
(3.23 kPa)
At higher elevations, the amount of BTU fuel
value delivered must be reduced by either:
• using gas that has been derated by the gas
company,
• changing the burner orifice to a smaller size
High
as regulated by the local authorities having
jurisdiction and by the (USA) National Fuel Gas
(Hi) 3.5" WC
Code NFPA 54/ANSI Z223.1 - latest edition or,
(0.87 kPa)
in Canada, the CAN/CSA-B149.1 codes - latest
(Hi) 10.0" WC
edition.
(2.49 kPa)
Install the appliance according to the regulations
of the local authorities having jurisdiction and,
in the USA, the National Fuel Gas Code NFPA
54 / ANSI Z223.1 - latest edition or, in Canada,
the CAN/CSA-B149.1 - latest edition.
NOTE: Flame appearance will diminish
4% per thousand feet of altitude.
Elevation 0-4500 feet ( 0-1372 meters)
Model
Series
MLBV-35
MLBV-40
Table 4
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Burner Orifice Sizes
Nat.Gas
Propane
drill size (inches)
drill size (inches)
#48 (0.076")*
#56 (0.046")*
H1236•
62L37•
#43 (0.089")*
#55 (0.052")*
99K75•
19L52•
*
Standard size installed at factory.
Part /Catalog Number.

GAS VALVE dIAGRAMS

See Figure 1 for millivolt models and Figure 2
for electronic models.
Pilot Adjustment
Main Gas Control Knob
Off/PILOT/ON
IN
OUT
Manifold Pressure Tap
Inlet Pressure Tap
Figure 1 - SIT Millivolt Gas Valve
Supply
Pressure-Tap
Regulator
Gas
(Manifold)
Mounting Screw
Inlet
PILOT
Pressure-Tap
Ground
Pilot Gas
(Inlet)
(TP)
Outlet
Figure 2 - Dexen Electronic Gas Valve
REqUIREMENTS fOR THE
COMMONWEALTH Of
MASSACHUSETTS
These fireplaces are approved for installation in
the US state of Massachusetts if the following
additional requirements are met:
• Install this appliance in accordance with
Massachusetts Rules and Regulations 248
C.M.R.
• Installation and repair must be done by a
plumber or gas fitter licensed in the Com-
monwealth of Massachusetts.
• The flexible gas line connector used shall
not exceed 36 inches (92 centimeters) in
length.
• The individual manual shut-off must be a
T-handle type valve.

NEW YORK CITY APPROVAL

New York City, NY (MEA)
These fireplaces are approved for installation
in New York City in the US state of New York
if the following additional requirement is met:
• An Outside Combustion Air Kit (FOAK-4,
FOAK-4LD, or DK-4) must be installed. See
Step 5 on Page 14.
Screw
HI/LO Variable
flame Height
Adjustment
Burner Stage
Terminal
Pilot Stage
Terminal