Keston Qudos 28s User, Installation And Servicing Instructions page 50

Fan powered high efficiency modulating domestic condensing gas system boiler
Table of Contents

Advertisement

WD420/3/2007
g.
Replace the burner head, inspecting the gasket for damage and replacing if
necessary, and reconnect the gas/air supply. Ensure the flanged gas/air supply
joint is air tight.
h.
Turn on the electrical supply to the boiler and allow the boiler to reach operating
temperature levels.
i.
Remove the combustion test point plug from the flue pipe. This is situated on the
flue spigot out of the cabinet.
j.
Carry the full procedure detailed in section 5.7 COMBUSTION TESTING -
MANDATORY
k.
Replace the combustion test point plug.
l.
Recheck the burner pressure by following the procedure detailed in Section 4.7.
m.
Check all joints for tightness up to the gas burner.
n.
Complete the Gas Boiler Commissioning Checklist - Service Interval Record
(Chapter 10).
Installation & Servicing Instructions
Chapter 7 : Servicing
The Keston Qudos 28s & Qudos 28sP Boilers
Page : 45