SPECIFICATIONS

Model No.
PTS/PTU 40/25
PTS/PTU 50/30
PTS/PTU 75/50
PTS/PTU 100/65
PTS/PTU 125/80
PTS/PTU 150/100 150,000 100,000
PTS/PTU 175/110 175,000 110,000
PTS/PTU 200/125 200,000 125,000
* MOUNT HEATERS AS HIGH AS POSSIBLE. Minimums are shown as a guideline for human comfort and uniform
energy distribution for complete building heating applications. Consult your Space-Ray representative for the
particulars of your installation requirements.
Type
Gas:
Natural
or Propane
1) See Section 16 for vent sizes when multiple heaters are connected into a common vent.
Module Electrical Rating:
Input Power-Control: 18-30 VAC
transformer)
Input Power-Line: 120 VAC (L1, IND contacts only)
Gas Valve Rating: 2.0 A @ 24 VAC (max.)
Combustion Blower Rating: 3.0 FLA @ 120 VAC
Flame Sensitivity: 0.7 microamps minimum
6.0)

PACKING LIST

A) PTS/PTU Burner Package
Burner Box Assembly (Refer to the following chart for Package Part Numbers)
4"ID x 4"Lg Flue Adapter Collar (#30504500) ...................................................................1
Fastener Kit – Burner Box Attachment/Flue Adapter Collar (#42907040)....................1
containing:
Tube Flange Gasket (#42921000).......................................................................................1
Turbulator 24" Long (#44152240) *See chart above for required quantities.
Installation & Operation Instructions (#43343530)..........................................................1
Turnbuckle (#30545040) ......................................................................................................1
Gas connector 5/8" OD x 36" (#30302360) .......................................................................1
Form #43343530
July 08
High
Low
Combustion
Btu/hr
Btu/hr
Air Plate
Input
Input
Part #
40,000
25,000
#44140061
50,000
30,000
#44140064 3.5mm
75,000
50,000
#44140063
100,000 65,000
#44140062
125,000 80,000
#44140066
#44140067
#44140067
#44140068 6.9mm
Gas-Pipe
Tube
Connection:
Diameter:
½" MPT
(Male)
4"
50/60 Hz (class 2
1/4 H.P. Motor
#10 x 1/2" Self-Drilling Screws (#02189020)..............................2
¼ - 20 Locknuts (#02167010) ..............................................................3
Orifice Size
Natural Gas
Propane Gas
#32
#49
(0.116)
46
(0.138)
#21
2.5mm
(0.159)
#12
#32
(0..189))
#4
#30
(0..209)
"A"
#27
(0.234)
"E"
#23
(0.250)
4.1mm
(0.272)
Flue
Fresh Air
Connection:
Connection:
1
4" Round
4" Round
Ignition System (direct spark):
15 second trial for ignition period
15 second pre-purge period
60 second inter-purge period
30 second post-purge period
3 tries for ignition (separate flame sensor).
–5–
Minimum *
Mounting Height
@
Horizonta
@
l
45º Angle
10 ft.
9 ft.
(0.073)
11 ft.
10 ft.
(0.081)
13 ft.
12 ft.
(0.098)
14 ft.
13 ft.
(0.116)
14 ft.
13 ft.
(0.129)
15 ft.
14 ft.
(0.144)
16 ft.
15 ft.
(0.154)
18 ft.
16 ft.
(0.161)
Electrical
Current
Supply:
Rating:
1
120 Volt,
60Hz, 1 Phase
1.74 Amp
QTY
1
*
Turbulator
Qty.
4
5
5
3
7
4
0