Condensate Drain Connection - Ferroli MODENA S HE Instructions For Use, Installation And Maintenance

Wall-mounted boiler
Table of Contents

Advertisement

Connection to multiple flues or single flues with natural draught
To connect the MODENA S HE boiler to a multiple flue or a single flue with natural draught, the flue or chimney must be
expressly designed by professionally qualified technical personnel in conformity with the current standards and regulations.
In particular, flues and chimneys must:
Be sized according to the method of calculation given in the standard.
Be tight with respect to the products of combustion, resistant to the fumes and heat and impermeable to condensate.
Have a circular or square cross-section (some hydraulically equivalent sections are permissible), with a vertical pro-
gression and with no constrictions.
Have the ducts conveying the hot fumes at a suitable distance or separately from combustible materials.
Be connected to just one unit per floor, for not more than 6 units (8 if there is a compensation duct or opening).
Have no mechanical suction devices in the main ducts.
Be at low pressure, all along their length, in conditions of stationary operation.
Have at their base a collection chamber for solid materials or condensate, of at least 0.5 m, equipped with an airtight
metal door.

2.7 Condensate drain connection

Installation
The boiler is equipped with an internal air-trap to drain off the condensate.
Fit the inspection coupling A and the hose B, pushing it on for approximately 3 cm and securing it with a clamp.
Fill the air-trap with approximately 0.5 ltrs of water and connect the hose to the waste system, or soakaway.
18
fig. 23
cod. 3541C364 - Rev. 00 - 12/2012
MODENA S HE
EN

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Modena 25 s heModena 32 s he18s

Table of Contents