OPTIMAX 25 C wall-mounted gas fi red, pre-mix condensing combination boiler INSTRUCTIONS FOR USE INSTALLATION AND MAINTENANCE G C N° 47-267-34...
Page 2
“This record must be completed and left with the end user”. Ferroli is a member of the Benchmark initiative and fully supports the aims of the programme. Benchmark has been introduced to improve the standards of installation and commissioning of central heating systems in the UK and to encourage the regular servicing of all central heating systems to ensure safety and efficiency.
2.4 Connection to the gas system ................13 2.5 Electrical Connections ..................13 2.6 Flue system ......................14 2.7 Condensate outlet connection ................20 2.8 Ferroli Optimax (optional) Time clock installation..........22 3. SERVICE AND MAINTENANCE............23 3.1 Adjustments ......................23 3.2 System start-up .....................24 3.3 Maintenance......................25 3.4 Troubleshooting....................27...
1.1 Introduction Dear Customer, Thank you for choosing Optimax 25 C, a FERROLI wall-mounted boiler of the latest generation, featuring advanced design and cutting-edge technology. Optimax 25 C is a high-efficiency condensing pre-mix appliance for heating with extremely low emis- sions, running on natural gas or LPG.
Optimax 25 C 1.2 Control panel °C °C fig. 1 1 - System temperature adjustment / Summer/Winter selection This knob is used to adjust the system temperature from 20°C to 90°C and can switch over between summer / winter. To increase the system temperature, turn the knob clockwise; anticlockwise to decrease it.
Optimax 25 C 1.3 Turning ON and OFF Ignition • Open the gas cock on the boiler. • Purge the air from the pipework upstream of the gas valve. • Ensure the power is on to the appliance. • Press the key to turn the appliance on (fig 1 item 2) •...
If the problem remains after two attempts at resetting, contact your nearest FERROLI Caresafe. For further fault codes, refer to section 3.4 “Troubleshooting”. Before calling the FERROLI Caresafe centre, check that the problem is not due to an installation error or there being no gas or electricity.
1.7 Optional Time Clock If a ferroli 24 hour time clock is fitted to the boiler this will control the central heating, the pre set times will only come into operation when both selector switches are moved to the “Auto” position.
Optimax 25 C 2. INSTALLATION 2.1 General Instructions This device must only be used for the purpose for which it is specially designed. This unit is designed to heat water to a temperature below boiling point and must be connected to a hea- ting system and/or a water supply system for domestic use, compatible with its performance, characteristics and its heating capacity.
Optimax 25 C 2.2 Boiler location The unit’s combustion circuit is sealed off from the installation room and therefore requires no compartment ventilation. The installation room must be sufficiently well ventilated to prevent any dangerous conditions from forming in the event of even slight gas leakage.
Optimax 25 C 2.3 Boiler water connections The heating capacity of the unit should be previously established by calculating the building’s heat requirement according to current regulations. For good operation and long life of the boiler, the plum- bing system must be well proportioned and always complete with all those accessories that guarantee regular operation and running, room thermostat, trv’s and automatic bypass etc.
Page 12
Optimax 25 C The isolation valve kit shown in Fig. 4 is supplied as standard. A = Nut B = Compression olive D = 3/4” seal (green) E = 1/2” seal (green) F = 1/2” gas seal (blue) G = Filter H = Cap Flow isolation valve Hot water connection...
Optimax 25 C Water treatment If treatment is used ferroli limited recommanded only the use of Fernox or Sentinel water treatment products, which must be used in accordance with the manufactures instructions. for further information contact: Fernox Manufacturing Co. LTD.
The current standards and local regulations must be observed. It should be noted that only Ferroli flue system and accessories should be used on this appliance, as per BS 5440 2000 and C.E. test certification.
Page 15
Optimax 25 C Connection with concentric fl ue system The unit can be connected to a concentric air/flue duct with a wall or rooftop outlet as shown on the following drawings. Numerous accessories are available on request to meet the various installation requirements.
Page 16
Optimax 25 C Vertical Outlet The total length in equivalent metres of the concentric flue must not exceed the maximum lengths stated in the following table, note that each bend gives rise to the stated reduction. For example, a duct = 60/100 composed of 1 bend of 90°...
Page 17
3. Check that the total calculated loss is less than or equal to 75 equivalent metres, i.e. the maximum permissible for this model of boiler. For complete flue options please contact ferroli or check our comprehensive flue manual. 1KWMA83W Table 3 Equivalent Ref.
KWMA85A Bend 45° Ø 80 mm male - female Vertical flue terminal KWMA65W KWMA84U Bend 90° Ø 80 mm male - female The stated loss values refer to genuine Ferroli fl ue accessories. KWMA01W Terminal Position D, E fig. 13...
Page 19
Optimax 25 C Minimum Dimensions of Flue Terminal Positions Directly below an opening, air brick, 300mm opening windows, etc. Above an opening, air brick, 300mm opening windows, etc. Horizontally to an opening, air brick, 300mm opening windows, etc. 75mm Below gutters, soil pipes or drain pipes 200mm Below eaves Below balconies or car port roof...
Optimax 25 C Connection to collective fl ues or single fl ues with natural draught If you are then going to connect the Optimax 25 C boiler to a collective flue or a single flue with natural draught, the flue must be expressly designed by professionally qualified technical personnel in conformity with the standards and rules in force.
Optimax 25 C Condensate discharge Where possible the condensate should discharge into an internal soil pipe or waste system. The minimum pipe diameter required is 22 mm, a trap has already been fitted to the appliance with a flexible tail to facilitate the connection to the condensate discharge pipe.
Optimax 25 C 2.8 Ferroli Optimax (optional) Time clock installation. - Remove outer case by removing four securing screws from the lower sides and lift off. - Remove two screws securing fascia panel and swing the fascia panel down. - Remove the four screws securing rear cover of the fascia and remove.
Optimax 25 C 3. SERVICE AND MAINTENANCE 3.1 Adjustments All adjustment and conversion operations must be carried out by Qualified Personnel such as ferroli Technical Service. FERROLI declines any responsibility for damage or physical injury caused by unqualified and unauthorized persons tampering with the device.
Optimax 25 C 3.2 System start-up Commissioning must be performed by Qualified Personnel. Checks to be made at first ignition, and after all maintenance operations that involved discon- necting from the systems or an intervention of a safety device. Before lighting the boiler: •...
3.3 Maintenance The following operations are strictly reserved for Qualified Personnel, such as corgi registered engineers or Ferroli personeer. Seasonal inspection of the boiler and fl ue It is advisable to carry out the following checks at least once a year: •...
Optimax 25 C Opening the casing To open the boiler casing, you need to follow the sequence given below and the instructions of fig. 17. 1 Using a screwdriver, fully unscrew and remove the 2 screws “A ” 2 Open by lowering the panel “B ” 3 Lift and take off the casing “C ”...
Optimax 25 C 3.4 Troubleshooting Fault Diagnosis In the event of operating problems or trouble, the display will flash and a fault identification code appears. There are faults that in order to restore operation the RESET button must be pressed (ref.2 - fig. 1); or if the boiler fails to start, it will be necessary to repair the fault (code nos.
Page 28
Optimax 25 C Fault Possible cause Cure Software fault • Software operating fault • Cut off and restore the electricity supply. If the trouble remains, check and/or change the CVBC No flame after the ignition • Detection electrode faut • Check that the electrode is correct positioned and is necessary change phase (5 times in 4 min.) •...
Optimax 25 C 4 TECHNICAL CHARACTERISTICS AND DATA 4.1 Dimensions and connections Top view System flow (22 mm with isolation valve fitted) DHW outlet (15 mm with isolation valve fitted) Gas inlet (22 mm with isolation valve fitted) Cold main inlet (15 mm with isolation valve fitted) System return - 22 mm with isolation valve fitted 77,5 57,5...
Hot water circuit connections (with isolation valve fitted) Ø15 Maximum length of separate flues D=80* (*Measurement given in equivalent linear metres – cfr FERROLI calculation system) Electrical power supply Max electrical power absorbed Electric power drawn by the circulator (Speed I-II-III)
Optimax 25 C 4.5 Diagrams Head available for the system fig. 22 1 - 2 - 3 = Pump selector positions (In order to obtain maximum hot water output the pump must be left in position 3). A =Boiler losses of head...
2 6 7 BENCHMARK BENCHMARK No. Please add the first 4 digits of the Boiler serial No to complete the BENCHMARK No. GAS BOILER COMMISSIONING CHECKLIST C O L L E C T I V E M A R K BOILER SERIAL No.
SIGNATURE SERVICE 10 SERVICE 9 DATE DATE ENGINEER NAME ENGINEER NAME COMPANY NAME COMPANY NAME TEL No. TEL No. CORGI ID CARD SERIAL No. CORGI ID CARD SERIAL No. COMMENTS COMMENTS SIGNATURE SIGNATURE FERROLI TECHNICAL HELPLINE - 08707 282 885...
Page 40
Should you require help during installation call our Technical Helpline on 08707 282 885 option 1 To book a Ferroli service engineer call Ferroli caresafe on 08707 282 885 option 2 Phone numbers: Installer Service Engineer BECAUSE OF OUR CONSTANT ENDEAVOUR FOR IMPROVEMENT DETAILS MAY VARY SLIGHTLY FROM THOSE QUOTED IN THESE INSTRUCTIONS.