Ferroli MODENA S HE Instructions For Use, Installation And Maintenance page 17

Wall-mounted boiler
Table of Contents

Advertisement

MODENA S HE
Position of terminals
A
Directly under an opening, air inlet, openable window, etc.
B
Above an opening, air inlet, openable window, etc.
C
Horizontally to an opening, air inlet, openable window, etc.
D
Under gutters, drain pipes
E
Under cornices or under eaves
F
Under balconies or garages
G
From a drain pipe or a vertical drain pipe
H
From an internal or external corner
I
Above ground level, a roof or balcony
J
From a surface facing the terminal
K
From a terminal facing the terminal
L
From a garage opening (e.g. door, window) with access to the home
M
Vertically from a terminal on the same wall
N
Horizontally from a terminal on the same wall
O
From the wall on which the terminal is fitted
P
From a vertical structure on the roof
Q
Above the intersection with the roof
N/A = Not applicable
Also, the terminal must be at least 150 mm (in case of forced intake) from an opening made in the structure of
the building to house a fitted element such as a window frame.
Positions of condensate drain terminals: if the fume exhaust is provided for at a low level, the potential effect of
NOTES
the flue gas cloud must be considered. Special flue gas management kits are available by request.
The flue gas cloud must not be directed towards:
-
A frequented approach
-
A window or door
-
An adjacent property
EN
fig. 22
Minimum dimensions of fume exhaust terminals
cod. 3541C364 - Rev. 00 - 12/2012
300 mm
300 mm
300 mm
75 mm
200 mm
200 mm
150 mm
100 mm
300 mm
600 mm
1200 mm
1200 mm
1500 mm
300 mm
N/A
150 mm
300 mm
17