Page 2
VHJ(DB)-SM of indoor unit Main functions and control specifications of outdoor unit Function of main thermistor Value of thermistor Caution for diagnosis 3 Error codes and description indoor display For indoor unit For outdoor unit ..................10.1 Indoor Unit ....................10.2 Outdoor Unit .....................
HSU24VHJ DB Connector Wiring Diagram 4.Printed Circuit Board Connector Wiring Diagram 4.1 Indoor unit Connectors 1) CN26 Connector for fan motor 2) CN1 Connector for heat exchanger thermistor and Room temperature thermistor 3) CN11` Connector for UP&DOWN STEP motor 4) CON2 Connector for power N wire 5) CON1 Connector for power L 6) CN32 Connector for display board 7) C0N6,C0N8 Connector for ions generator...
Page 12
HSU24VHJ DB Connector Wiring Diagram CN32 CN11 CN48 CON6 CON8 CON1 CON2 CN26 Domestic Air Conditioner...
Page 13
HSU24VHJ DB Connector Wiring Diagram Domestic Air Conditioner...
HSU24VHJ DB Connector Wiring Diagram outdoor unit 1) CN1,CN2 Connector for power N and L 2) CN3 Connector for ground 3) CN22 Connector for DC POWER 15Vand 5V to the module board 4) CN16 Connector for electric expansion valves 5) CN21 Connector for DC fan motor 6) CN10 Connector for four way valve coil 7) CN17,CN18,CN19,CN20 Connector for thermistors (CN20: outdoor air,CN19: heat exchanger, CN18 :SUCK thermistors ,CN17 :discharge pipe)
This specification use for HSU18VHJ DB frequency conversion air condition are manufactured by Haier air condition parent company. "Setting value" (express in parameter) in this specification means is a parameter that is stored in EEPROM. Refer to [EEPROM parameter table].
HSU24VHJ DB Funcitions and Control When the compressor is working and the max setting for indoor fan motor is medium or weak, the upper limit of indicated frequency is as follows: Frequency control form for wind volume Limited frequency Limited frequency variables Medium wind volume FQLIMMD...
HSU24VHJ DB Funcitions and Control 20 seconds after the compressor stops, the up wind volume is weak (switching to SSLO in silent running mode) and then slightly weak. While the down wind volume is stoped If the compressor stops when the heat running starts, the wind volume is weak Under the dehumidification mode the fan motor stops as the compressor stops The operation is weak after 3 minutes’...
Page 20
HSU24VHJ DB Funcitions and Control When in automatic mode, there are powerful and silent functions for your choice. When the main unit is in cooling mode, it operates with powerful cooling or silent cooling. When the main unit is in heating mode, it operates with powerful heating or silent heating.
Page 21
HSU24VHJ DB Funcitions and Control a. After setting the sleeping function, the refrigerating mode and dehumidification mode will run as per the following rules: 1 hour 1 hour 6hours T( ) Ts+4 Ts+2 b.After setting the sleeping function, the heating mode will run as per the following rules: T( ) 1 hour 1 hour 3hours...
Page 22
HSU24VHJ DB Funcitions and Control To enter into the function please press the sleep key 10 times with 4 beeps in 7 seconds Under the power failure compensation mode, unplug and plug again ,the indoor unit will resume original operation Under the power failure compensation mode, unplug and plug again, the unit will be on OFF state.
HSU24VHJ DB Funcitions and Control 5.2 Main functions and control specification of outdoor unit Sensor Code Definition: Tai= Indoor Ambient Temperature, Tao=Outdoor Ambient Temperature, Tc1=Indoor Coil, Td= Air Discharge, Te= Outdoor Coil, Ts=Air Intake 5.2.1 Outdoor Unit Operation Frequency and Control Compressor Operation Frequency Range: Outdoor Temperature ≤4...
HSU24VHJ DB Funcitions and Control TE≤C×TA α Among which: C:TA 0 C=0.8 TA≥0 C=0.6 For area prone to frost, the value is set at 6 when unit leaves the factory. Defrosting entry temperature control -15 ≤C×TA α≤-5 time interval between two defrosting cycles is 45 minutes. When defrosting begins, compressor will stop for one minute, external fan is running and 50s later, four-way valve will be off.
HSU24VHJ DB Funcitions and Control 5.2.6 System Protection Function Time interval between compressor shutdown and restart is set at 3 minutes to ensure that compressor will only restart after 3-minute shutdown and initial energization valves are turned on to adequate opening position after being fully turned off.
Page 27
HSU24VHJ DB Funcitions and Control Cooling: When outdoor temperature is lower than 23 , cooling operation will start, compressor frequency is limited to less than 50 HZ, outdoor wind speed is forced at level 1. Heating: When outdoor temperature is higher than 18 , heating operation will start, compressor frequency is limited to less than 53 HZ, outdoor wind speed is forced at level 1.
HSU24VHJ DB Funcitions and Control 5.3 Function of Main Thermistor A:Outdoor suction temperature sensor B: Exhaust temperature sensor C: Indoor heat-exchange sensor The outdoor heat exchanger thermistor is used for controlling target discharge temperature. The system sets a target discharge temperature according to the outdoor and indoor heat exchanger temperature, and controls the electronic expansion valve opening so that the target discharge temperature can be obtained.
system configration VHJ(D B)-SM Operation Press CLOCK button, "AM" or "PM" flashes. Press to set correct time. Each press will increase Emergency Operation: or decrease 1min. If the button is kept pressed,time will Use this operation only when the change quickly. After time setting is confirmed,press SET, remote controller is defective or lost.
Page 47
system configration VHJ(D B)-SM Operation In AUTO mode The unit operates in corresponding sleep Before going to bed, you can simply press the mode adapted to the automatically selected SLEEP button and unit will operate in SLEEP operation mode. mode and bring you a sound sleep. 4.
Page 48
VHJ(DB)-SM system configration Operation IMPORTANT INFORMATION REGA- Set clock correctly before starting TIMER operation. RDING THE REFRIGERANT USED 1.After unit starts, select your desired operation mode. 2.Press TIMER button to change TIMER mode. Every Contains fluorinated greenhouse gases time the button is pressed, display changes as follows: covered by the Kyoto Protocol Remote controller: R410A...
system configration VHJ(DB)-SM Maintenance For Smart Use of The Air Conditioner Remote Controller Indoor Body Setting of proper room Do not block the air inlet temperature or outlet Proper Wipe the air conditioner by using a soft and temperature dry cloth.For serious stains,use a neutral detergent diluted with water.Wring the water Do not use water wipe the controller with a out of the cloth before wiping.then wipe off...
Page 50
VHJ(DB)-SM system configration Cautions WARNING Please call Sales/Service Shop for the Installation. Do not attempt to install the air conditioner by yourself because improper works may cause electric shock, fire, water leakage. WARNING Check proper When abnormality such as burnt-small found, Use an exclusive immediately stop the operation button and power source...
VHJ(DB)-SM system configration Trouble shooting Cautions grille of the air Do not obstruct or cover the ventilation Before asking for service, check the following first. conditoner.Do not put fingers or any other things into the inlet/outlet and swing louver. Do not allow children to play with the air conditioner .In no Phenomenon Cause or check points...
HSU24VHJ DB Service Diagnosis 7 Service Diagnosis 7.1 Caution for Diagnosis The operation lamp flashes when any of the following errors is detected. 1.When a protection device of the indoor or outdoor unit is activated or when the thermistor malfunctions, disabling equipment operation. 2.When a signal transmission error occurs between the indoor and outdoor units.In either case, conduct the diagnostic procedure described in the following pages.
HSU24VHJ DB Service Diagnosis 7.3.Error Codes and Description indoor display Code indication Reference Outdoor Description Page indoor (LED1 flash times) Indoorand Outdoor Communication fault between indoor and Page . outdoor units Room temperature sensor failure Page . Indoor Malfunction Heat-exchange sensor failure Page .
Page 54
HSU24VHJ DB Service Diagnosis 7.3.1Thermistor or Related Abnormality (indoor unit) : Room temperature sensor failure : Heat-exchange sensor failure the temperatures detected by the thermistors are used to determine thermistor errors when the thermistor input is more than 4.92V or less than 0.08V during compressor operation.
HSU24VHJ DB Service Diagnosis 7.4.2 Indoor fan motor malfunction The rotation speed detected by the Hall IC during fan motor operation is used to determine abnormal fan motor operation when the detected rotation feedback singal don’t receiced in 2 minutes Operation halt due to breaking of wire inside the fan motor .
Page 56
HSU24VHJ DB Service Diagnosis Turn off power supply and rotate fan by hand Does fan rotate Replace fan motor smoothly? Turn power ON and operate fan Turn off power supply and disconnect fan motor connector,then turn power ON Does it rotate? Check output of fan motor connector I s m o t o r p o w e r voltage DC310V...
HSU24VHJ DB Service Diagnosis 7.3.3 IPM protection LED1 flash 2 times: IPM protection is detected by checking the compressor running condition and so on. The system leads to IPM protection due to over current The compressor faulty leads to IPM protection circuit component of IPM is broken and led to IPM protection IPM protection dues to the compressor faulty IPM protection dues to faulty PCB of IPM module...
Page 58
HSU24VHJ DB Service Diagnosis Ω to several MΩ ( ) Unacceptable resistance Short (0 Ω) or open 7.3.4 The IPM and outdoor PCB don’t communicate or Related Abnormality LED1 flash 4 times Indoor Display Communication is detected by checking the IPM module and the outdoor PCB The outdoor PCB broken leads to communication fault The IPM module broken leads to communication fault The outdoor PCB is broken...
HSU24VHJ DB Service Diagnosis 7.3.5 Thermistor or Related Abnormality(outdoor unit) LED1 flash 10 times: LED1 flash 13 times: LED1 flash 12 times: LED1 flash 11times: This type of error is detected by checking the thermistor input voltage to the microcomputer. (A thermistor error is detected by checking the temperature) The thermistor input is above 4.9V or below 0.1V with the power on.
HSU24VHJ DB Service Diagnosis 7.3.6 Overheat Protection For Exhaust Temperature LED1 flash 8 times the exhaust temperature control is checked with the temperature being detected by the exhaust pipe thermistor when the compressor discharge temperature is above 117 Electronic expansion valve defective Faulty thermistor Faulty PCB Be sure to turn off power switch before connect or disconnect connector,...
Page 61
HSU24VHJ DB Service Diagnosis Pull out the exhaust sensor and measure its The sensor is damaged. Replace the sensor resistance standard temperatures with a new one. according to the resistance-temperature table The sensor is damaged. Replace the sensor the results deviate with a new one.
HSU24VHJ DB Service Diagnosis 7.3.8 Communication error between the indoor and outdoor units LED1 flash 15 times The date received from the another unit in indoor unit-outdoor unit signal transmission is checked whether is normal When the date sent from the another unit cannot be received normally,or when the content of the data is abnormal indoor unit- outdoor unit signal transmission error due to wiring error Faulty PCB...
Page 63
HSU24VHJ DB Service Diagnosis Check the status of LED1 on the indoor mainboard. If the LED1 blinks measure voltage between Jumpers 3 and 4 of IC8 on the indoor mainboard with a multimeter. Test the outdoor power supply (230VAC and +310VDC) with a multimeter.
Page 64
HSU24VHJ DB Service Diagnosis 7.3.10 Power Supply Over or under voltagve fault LED1 flash 6 times An abnormal voltage rise or fall is detected by checking the specified voltage detection An voltage signal is fed from the voltage detection circuit to the microcomputer Supply voltage not as specified the IPM module is broken the outdoor PCB is broken...
HSU24VHJ DB Service Diagnosis 7.3.11 Loop of the station detect error LED1 flash 18 times LED1 flash 19 times the position of the compressor rotor can not detected normally when the The wiring of compressor is wrong or the connection is poor; the compressor is damaged Faulty The wiring of compressor Faulty compressor...
HSU24VHJ DB Service Diagnosis 7.3.12 Over-current of the compressor LED1 flash 3 or 24 or 25 times The current of the compressor is too high when the IPM Module is damaged the compressor is damaged power supply. voltage is too low or too high Faulty IPM Module Faulty compressor Faulty power supply...
Page 67
HSU24VHJ DB Service Diagnosis 7.3.13Fan Motor(DC Motor) or Related Abnormality LED1 flash 9 times The rotation speed detected by the Hall IC during fan motor operation is used to abnormal fan motor operation when the detected rotation feedback singal don’t receiced in 2 minutes Operation halt due to short circuit inside the fan motor winding.
Page 68
HSU24VHJ DB Service Diagnosis Turn power supply and rotate fan by hand Does fan rotate Replace the motor smoothly? Turn power ON and operate fan Turn power supply disconnect motor connector,then turn power ON Does rotate? Check output of fan motor connector Is motor power voltage DC310V gengerated? Replace indoor unit PCB...
VHJ(DB)-SM Installation Manual of Room Air Conditioner Preparation Selection of Installation Place Necessary Tools for Installation Indoor Unit - Select a location that is Torque wrench Hammer (17mm,22mm,26mm) Nipper Robust not causing vibration, where the body can be supported s Hacksaw Pipe cutter Not affected by heat or steam generated in the vicinity, where inlet and outlet of the...
Page 70
VHJ(DB)-SM [ Left · Left-rear piping ] Accessory parts In case of left side piping, cut away, with a nipper, the lid for left piping. In case of left-rear piping, bend the pipes according to the piping direction to Drain hose (1) Remote controller (1) the mark of hole for left-rear piping which is marked on heat insulation materials.
Page 71
VHJ(DB)-SM Ensure that no dirt or debris enters the pipe. Outdoor unit The standard pipe length is 7m (27 9/16) . If it is over 7m (27 9/16) , the function of the unit will be affected. If the pipe has to be lengthened, the refrigerant should Indoor uni t be charged, according to 20 g/m (0.018 oz/inch).
Page 72
VHJ(DB)-SM No gas leakage? On Drainage In case of gas leakage, tighten parts of pipe connection. If leakage stops, Please install the drain hose so as to be downward slope without fail. then proceed Please don’t do the drainage as shown below. Detach the charge hose from the service port, open 2-way valve and 3-way.
9 Removal of Procedure 9.1 Removal of Procedure of HSM24HEA03/R2(DB) indoor unit 9.11 Removal of Front panel Procedure Warning Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work. Step Procedure Points 1. Remove the front panel. Open the front panel to the horizontal position.
Page 74
Step Lift an air filter upwards slightly and then pull it out downwards. Insert the air filters along grooves when installing. When installing, insert 2 hooks of the air filter completely. Domestic air conditioner...
Page 75
9.13 Removal of Horizontal Blade and Front Grill Procedure Warning Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work. Step Procedure Points 1. Remove the horizontal The horizontal blade is blade. single. Release the center pivot.
Page 76
Step Loosen the marked f ive screws Release the marked four hooks. When assembling, install the front grille horizontally so as not to stuff the flap inside. When assembling, make sure the three hooks are caught prop e rly. Domestic air conditioner...
Page 77
9.14 Removal of Drain Pan Procedure Warning Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work. Step Procedure Points Remove the front grille. Remove the assembly of the reduction motor. 1. Remove the Drain pan. Loosen the marked screws under the screw covers...
Page 78
9.15 Removal of Vertical Blade and Swing Motor 9.15 Removal of Vertical Blade and Swing Motor Procedure Warning Be sure to wait 10 minutes or more after turning off all power supplies Procedure Warning Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work.
Page 79
9.16 Removal of Electrical Box Procedure Warning Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work. Step Procedure Points Remove the front grille. Discharge the static electricity from your body 1. Remove the electrical before touching the electrical box.
Page 80
9.17 Removal of Heat Exchanger Procedure Warning Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work. Step Procedure Points You can detach the indoor unit without removing the assembly of the outlet grille. Loosen the screws Caution fixed to the installation...
Page 81
9.18 Removal of Fan and Fan Motor Procedure Warning Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work. Step Procedure Points Loosen the screws. Remove the right side plate. Domestic air conditioner...
Page 82
9.2 Removal of Procedure 9.21 Removal of Front panel Procedure Warning Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work. Step 1. Remove the front panel. Open the front panel to the horizontal position. Release the both sides pivots and remove the front panel.
Page 83
Step Procedure Points Lift an air filter upwards slightly and then pull it out downwards. Insert the air filters along grooves when installing. When installing, insert 2 hooks of the air filter completely. Domestic air conditioner...
Page 84
9.23 Removal of Horizontal Blade and Front Grill Step Loosen the marked f ive screws Release the marked four hooks. When assembling, install the front grille horizontally so as not to stuff the flap inside. When assembling, make sure the three hooks are caught prop erly.
Page 85
Procedure Warning Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work. Step Procedure Points 2. Remove the horizontal The horizontal blade is blade. single. Release the center pivot. blade Installation procedure 1. Since key pattern hook is provided, rotate the blade and fit it to the left pivot first.
Page 86
Step Procedure Points Pull the front grille out horizontally and remove When assembling, install the front grille horizontally so as not to stuff the flap inside. When assembling, make sure the three hooks are caught properly. Domestic air conditioner...
Page 87
Procedure Warning Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work. Step Procedure Points Remove the front grille. Remove the assembly of the reduction motor. 1. Remove the Drain pan. Loosen the marked screws under the screw covers Loosen the marked...
Page 88
9.25 Removal of Vertical Blade and Swing Motor Procedure Warning Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work. Step Procedure Points Loosen the marked screws Push the hooks on the back of the vertical blades and remove.
Page 89
9.26 Removal of Electrical Box Procedure Warning Be sure to wait 10 minutes or more after turning off all power supplies Procedure Warning Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work. before disassembling work.
Page 90
9.27 Removal of Heat Exchanger Procedure Warning Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work. Step Procedure Points You can detach the indoor unit without removing the assembly of the outlet grille. Loosen the screws Caution fixed to the installation...
Page 91
9.28 Removal of Fan and Fan Motor Procedure Warning Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work. Step Procedure Points Loosen the screws. Remove the right side plate. Domestic air conditioner...
Removal of procedure (DB) 9. The removal procedure of outdoor 9. .1 Removal of Outdoor panel Step Procedure Points 1. Features Loosen the service Be careful not to cover screw and remove the service cover. Domestic air conditioner...
Page 93
Removal of procedure Step Procedure Points 2. Remove the panels. Loosen the 4 screws and lift the top panel Loosen the screws of the panel. Pull and remove the front panel. Domestic air conditioner...
Page 94
Removal of procedure Removal of procedure 9. .2 Romoval of Electrcal Box Step Procedure Points screws, then lift the electrical box Domestic air conditioner...
Page 95
Removal of procedure Removal of procedure 9. .3 Romoval of the Side panel Step Procedure Points screws and remove the side panel. Domestic air conditioner...
Page 96
Removal of procedure Removal of procedure Step Procedure Points Remove the screws and remove the side panel. Domestic air conditioner...
Removal of procedure Removal of procedure 9. .4 Removal of fan and fan motor Step Procedure Points Put the lead wire Loosen the of motor when remove the fan the propeller fan) Domestic air conditioner...
Page 98
Removal of procedure Removal of procedure Step Procedure Points screws and lift the fan motor. Domestic air conditioner...
Page 99
Removal of procedure Removal of procedure Step Procedure Points screws, then lift the Domestic air conditioner...
Page 100
Removal of procedure Removal of procedure Step Procedure Points screws, then lift the proof plate. Domestic air conditioner...
Page 101
Removal of procedure Removal of procedure Step Procedure Points Cut down the and pull out the compressor and remove the Domestic air conditioner...
Page 102
Removal of procedure Removal of procedure Step Procedure Points Domestic air conditioner...
Page 103
Removal of procedure Removal of procedure Step Procedure Points Domestic air conditioner...
Page 104
Removal of procedure Removal of procedure Step Procedure Points Remove the Domestic air conditioner...