Specifications,
continued
AGA56.43A...
AGA56.9A
ASZ... Potentiometers
Page 28
AGA56.43A... Electronic circuit boards
Input signal
Impedance
Voltage input
AGA56.9A... Multi function electronic
circuit boards
Operating voltage
Operating frequency
Input signals
Impedance
Current input
Voltage input
Output signals
Max output load
Current output
Voltage output
Zero adjustment
Span adjustment
Split ranging (SHIFT)
Input signal override (POS)
Ambient operating temperature
Shipping temperature
Auto/manual switch
Manual toggle switch
Weight
ASZ... Potentiometers
Versions
Resistor values
Hysteresis
SQM5... Reversing Actuators
Same specifications as AGA56.41A
except:
0 to 10 Vdc
≥100K Ω
Single potentiometer
ASZ... (1000 ohm) is required
24 Vac +10%-15%
110 Vac -15% to 120 Vac +10%
220 Vac -15% to 240 Vac +10%
50 to 60 Hz
4 to 20 mA
0 to 20 mA
0 to 10 Vdc
0 to 135 ohm
≤300 Ω
≥100K Ω
4 to 20 mA
0 to 20 mA
0 to 10 Vdc
<600 ohm
> 1.5K ohm
MIN: 0 to 75%
MAX: min-100%
4 to 20 mA on terminal ZF
Line voltage (... Vac) on terminal P
adjust with POS potentiometer
-5°F to 140°F (-20°C to 60°C)
-58°F to 140°F (-50°C to 60°C)
2-position switch
3-position switch
0.7 lb (0.33 kg)
Single and double potentiometer
See Table 2 and Data Sheet 7921.
< 0.3% related to drive shaft
Siemens Building Technologies, Inc.