Switch Setting - Modem A - Patton electronics 2085RC User Manual

Rs-232 to rs-485 converter: dual port rack mount card
Table of Contents

Advertisement

S1-3: Carrier Control
The setting for switch S1-3 determines whether the carrier is
"Constantly On" or "Controlled by RTS". This setting allows for opera-
tion in switched carrier, multipoint and/or hardware handshaking appli-
cations.
S1-3
Setting
On
Controlled by RTS
Off
Constantly ON
S1-4: Echo Mode
The setting for switch S1-4 determines whether the Model 2085RC
echoes data back to the transmitting device (half-duplex mode only).
S1-4
Setting
On
Echo On
Off
Echo Off
SWITCH SET "S2"
DIP switch S2 is used to configure transmit impedance, and
2-wire/4-wire operations. The summary table below shows the factory
default settings for switch S2. Following the summary table is a
detailed description of each individual switch.
SWITCH S2 SUMMARY TABLE (factory defaults in bold)
Position
Function
S2-1*
TX OFF Impedance
S2-2*
TX OFF Impedance
S2-3*
2-Wire/4-Wire
S2-4*
2-Wire/4-Wire
*Note:
Switches S2-1 and S2-2 must be switched simultaneously.
Switches S2-3 and S2-4 must be switched simultaneously.
ON Position
OFF Position
Intermediate
High
Intermediate
High
2-Wire
4-Wire
2-Wire
4-Wire
7
S2-1 and S2-2: "Transmit Off" Impedance
Switches S2-1 and S2-2 are set together to determine whether the
receiving device "sees" the impedance of the Model 2085RC's transmit-
ter as being "high" or "intermediate" when the transmitter is turned off.
The "intermediate" setting is useful in half-duplex environments where
the receiving device does not respond well to the "high" setting.
S2-1
S2-2
Setting
On
On
Intermediate Impedance
Off
Off
High Impedance
S2-3 and S2-4: 2-wire/4-wire Modes
Switches S2-3 and S2-4 are set together to determine whether the
Model 2085RC is in 2-wire or 4-wire operating mode. Note: 2-wire
mode is half-duplex only.
S1-2
S1-3
Setting
On
On
2-wire mode
Off
Off
4-wire mode
3.1.2 SWITCH SETTINGS - MODEM "B"
DIP switches S3 and S4 configure converter B on the Model
2085RC front card. The tables below provide an overview of converter
B switch settings, including factory default settings. Following each fig-
ure is a detailed description of each switch's function.
SWITCH SET "S3"
DIP switch S3 is used to configure receive impedance, RTS/CTS
delay, carrier control operation and "echo" enable/disable. The summa-
ry table below shows the factory default settings for switch S3.
Following the summary table is a detailed description of each individual
switch.
SWITCH S3 SUMMARY TABLE (factory defaults in bold)
Position
Function
S3-1
RX Impedance
S3-2
RTS/CTS Delay
S3-3
Carrier Control
S3-4
Echo Mode
ON Position
OFF Position
120 Ohm
16K Ohm
8 msec
No Delay
RTS Controlled
Constantly On
Echo ON
Echo OFF
8