Binary Output (Relay Output) Troubleshooting - Trane Tracer MP503 Installation And Operation Manual

Input/output module
Hide thumbs Also See for Tracer MP503:
Table of Contents

Advertisement

Table 14. Binary output (relay output) troubleshooting of external wiring
Step number
Step 1
Perform the initial troubleshooting steps described in Table 13 on page 32
and verify that general board operation is okay.
Step 2
Inspect the wiring. Is there a good connection between the wire and the ter-
minal blocks? Look for shorts or opens. Pay particular attention to wire
splices.
Step 3
Look at the status LED for the binary output you are troubleshooting. (See
"Binary output LEDs" on page 28.) If the LED is on, the Tracer MP503 is
energizing its output relay.
Use your meter (set to measure ac voltage) to measure the voltage across the
binary output terminals you are troubleshooting on the Tracer MP503.
If the voltage is approximately 24 V, the problem lies beyond the Tracer
MP503. Is the wiring to the equipment good? Is there a pilot relay and is it
functioning correctly? Is a Hand-Off-Auto (HOA) switch overriding the
equipment?
If the voltage is approximately 0 V, proceed to the next step.
Step 4
Remove the wires from the binary output terminals and measure the voltage
again.
If the voltage is 24 V, there is a wiring or equipment problem external to the
Tracer MP503.
If the voltage is still approximately 0 V, the Tracer MP503 is commanding the
output to be off and you need to investigate the Tracer MP503 further. See
Table 15 on page 34 to troubleshoot the configuration and operation of the
binary output.
CNT-SVX09B-EN
Binary output (relay output)
troubleshooting
If a binary output (relay output) is not turning on the equipment wired to
it, then follow the troubleshooting steps in Table 14. Perform the steps in
the order they are listed.
The troubleshooting steps assume the equipment connected to the binary
output is off when you think it should be on. The steps are nearly the
same if the equipment is on when you think it should be off.
Action

Binary output (relay output) troubleshooting

Probable cause
General board
problem
Wiring problem
Wiring problem
Wiring problem
33

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents