Figure I-P-7 . Temporary manual override run
mode screen.

Option Menu and Keypad Operation

The operation menu sets all
programmable options built into your
ZSM. All options are retained in
permanent EEPROM memory.
To access the option menu display,
simultaneously depress and hold the
mode button and program button for four
seconds.
The example in Figure I-P-8 shows option
15 displayed and indicates the initial timer
setting in the temporary override run
mode. The option value shown is in
hours, and value selected is five hours.
When the option menu displays, the only
active buttons are the ↑ or ↓ arrow and
the "minus" and "plus" button. The ↑ or
↓ arrow increment through the available
options by number (1-24), and the
"minus" and "plus" button toggles
through the various option values
associated with each option number. See
Table I-P-1.
Note: On both programmable zone sensor
options, changing either option 9 or 10 will
erase the current program. To avoid
reprogramming, set options 9 and 10
before programming.
52
Installation
Table I-P-1. Zone Sensor BAYSENS019 Option Menu Settings.
Option #
Description
1
Morning Warm-up
2
Economizer minimum
Position override
3
Temperature Scale
4
Supply Air Tempering
5
Time Clock
6
Smart Fan
7
Intelligent Temperature Recovery
8
Programmable Days/Week
9
Programmable Periods/Day
10
Programmable Fan Operation
11
Remote Sensor Installed
12
Check Filter Interval
13
Display Zone Temperature
14
Keypad Lockout Enabled
15
Initial Time Setting in Temporary
Override Mode (hrs.)
16
Buzzer Options
17
Zone Temperature Calibration
18
Baud Rate
19
CV or HP Operation
20
Default Cooling setpoint
21
Default Heating setpoint
22
Minimum Cooling Setpoint
23
Maximum Heating Setpoint
Figure I-P-8. Typical option menu screen.
Programming
Value
0 = Disabled
1 = Enabled
0 = Disabled
1 = Enabled
0 = Fahrenheit
1 = Enabled
0 = Disabled
1 = Enabled
0 = 12 hours
1 = 24 hours
0 = Disabled
1 = Enabled
0 = Disabled
1 = Enabled
0 = 7 days (M,T ,W,T ,F ,S,S)
1 = 3 days (M-F , S, S)
2 = 2 days (M-F , S,S)
2,3,4
0 = Disallowed
1 = Allowed
0 = No
1 = Yes
0 = Disabled
3000 to 50 in 50 hour
increments
0 = No
1 = Yes
0 = Disabled
1 = Enabled
1,2,3,4,5
0 = Key Press only
1 = Key Press & Check filter
2 = Key Press, Check Filter,
and System Failures
Displays current temp.
with any offsets
0 = 1024 baud
1 = 1200 baud
0 = CV
1 = HP
45 to 98 F
43 to 96 F
45 to 98 F
43 to 96 F
Factory Setting
0
1
0
0
0
1
0
0
4
0
0
350
1
1
3
1
0 offset
1
0
74 F
68 F
45 F
96 F
SCXF-SVX01B-EN