Selection Procedures; Number Of Compressors Per Unit; Scwf/Siwf Compressor Electrical Data; Fan Without Vfd Data - Trane IntelliPak Signature Series Installation, Owner, And Diagnostic Manual

Commercial self-contained signature series, 20-80 ton, “bo” and later design sequence
Hide thumbs Also See for IntelliPak Signature Series:
Table of Contents

Advertisement

Selection Procedures

RLA = Rated Load Amps
Compressor LRA = Locked Rotor Amps
Fan Motor LRA = Locked Rotor Amps,
N.E.C. Table 430 - 150
FLA = Full Load Amps, N.E.C.
Table 430 - 150
Voltage utilization range is ±10 percent
Determination of minimum circuit
ampacity (MCA).
MCA = 1.25 x largest motor amps/VFD
amps (FLA or RLA) + the sum of the
remaining motor amps.
Determination of maximum fuse size
(MFS) and maximum circuit breaker size
(MCB).
MFS and MCB = 2.25 x largest motor
amps (FLA or RLA) + the sum of the
remaining motor amps.
For units with the dual power option,
there are two electrical circuits that need
calculations using the formulas above:
circuit #1 - fans
circuit #2 - compressors
If the rating value determined does not
equal a standard current rating of over
current protective device, use the next
lower standard rating for the marked
maximum rating.
SCXF-SVX01B-EN
Installation
Table I-ER-1. Number of Compressors per Unit
SCRF/SIRF
20
25 - 29
SCWF/SIWF 20 - 25
29 - 32
10
2
1
15
-
1
Table I-ER-2. SCWF/SIWF Compressor Electrical Data
200V
HP
RLA
LRA
10
33
269
15
46
409
Table I-ER-3. SCRF/SIRF Compressor Electrical Data
200V
HP
RLA
LRA
10
36.8
269
15
61.1
409
Table I-ER-4. Fan without VFD Data
200V
HP
FLA
LRA
5
16.1
105
7.5
25.0
152
10
32.9
193
15
44.8
290
20
61.0
373
25
74.0
469
30
87.0
552
40
113.0
718
50
NA
NA
Table I-ER-5. Fan with VFD
HP
FLA
7.5
29.4
10
37.9
15
51.4
20
66.5
25
91.4
30
91.4
40
116.0
50
NA
Table I-ER-6. Electric Heat - Single Stage
SCWF
SCRF
Size
Size
20
-
22
-
25
20
29
25
32
29
35
30
38
35
42
-
46
40
52
-
58
50
65
-
72
-
80
60
Note: Electric heat amperage should not be considered when determining minimum circuit ampacity. The current of the
unit in the heating mode will not exceed the current of the unit in the cooling mode.
Electrical
Requirements
30 - 35
40
50
35 - 38
42 - 46
52 - 58
3
2
-
1
3
460V
575V
RLA
LRA
RLA
14.5
117
11.5
20.5
178
16.5
460V
575V
RLA
LRA
RLA
16.3
117
13.2
26
178
21.5
460V
575V
FLA
LRA
FLA
6.7
46
5.4
10.8
66
8.2
14.2
84
11.4
20.3
126
16.2
25.0
162
20.0
31.0
204
24.2
36.0
240
28.6
47.8
312
38.0
62.0
390
49.2
200V
LRA
FLA
152
13.9
193
17.6
290
24.8
373
31.9
469
44
552
44
718
57.1
NA
68.3
Heat
200V
Kw
Amps
18
50
18
50
18
50
23
63.8
23
63.8
27
75
27
75
31.5
87.4
31.5
87.4
39
108.3
39
108.3
48
133.2
48
133.2
48
133.2
60
65 - 72
80
-
1
-
3
4
LRA
94
143
LRA
94
143
LRA
37
54
66
102
132
162
192
246
312
460V
LRA
66
84
126
162
204
240
312
390
460V
Amps
21.7
21.7
21.7
27.7
27.7
32.5
32.5
37.9
37.9
46.9
46.9
57.7
57.7
57.7
27