Electrical
Vitocontrol - Accessories
Note: The control system components below are
reserved for the PYROTEC Single-unit System.
With the PYROTEC Double-unit System, these
functions are included in the PYROTEC Mastercontrol.
Hot Water Storage Tank Management System, 5 Sensors
Function:
Using a heat accumulator improves the modulating output
operation of the PYROTEC grate firing system. In addition,
sudden heat requirement peaks are covered. The accumulator's
load of heat is detected by the temperature sensors. The
degree to which the accumulator is loaded is determined
by the external temperature sensor. The firing power is
adapted to the accumulator's degree of loading.
Supplied with:
-
4 additional PT100 sensors with sensor well,
1/2" x 280 mm
-
1 outdoor temperature sensor, uninstalled
Output signals 0 - 10 V
Function:
The system includes output of the boiler in the form of a
voltage signal and preparation for connection to receive a
maximum limitation of the boiler output.
Supplied with:
-
Output of the boiler, 0 - 10 V
-
Reception and processing of an external output limitation
0 - 0.5 V..... OFF
0.6 - 3 V..... Maintain embers
3.1 - 10 V... 30% to 100% output operation
Note: Installation of "Output signals 0 - 10 V" is possible
according to irrespective of any additional control
system components to be used.

Electrical Components

24
Operational Message
Function:
System status "Operating Load" indication; from
operation of the boiler pump to higher-level control.
Supplied with:
-
Floating output (operational message)
Export System for Operational Data
Function:
Output of all relevant operational data and error reports for
the PYROTEC Boiler Plant via MOD-BUS in the form of an
ASCII-data record via serial interface to higher-level control
equipment of the customer's. All the adjustable parameters
can be changed via the higher-level control equipment as
long as the control equipment provides for this.
Supplied with:
-
Interface on the control panel
-
Software component
-
MOD-BUS protocol (baud rate 9600)
Visualization by web server
Function:
A complete package for transmitting all data to a remote
computer for visualization, remote maintenance and
archiving of operational data for the PYROTEC Boiler
Plant. The hardware and software are integrated in the
Vitocontrol control system. All the adjustable parameters
can be changed from the remote computer.
Customer supplied:
-
IP address configuration