282
•
Can I run CX-Supervisor Runtime as a restricted Windows User?
CX-Supervisor (and CX-Server) require Administrator rights to be
installed on a computer, but other users can then run the software. The
runtime will run without problems as a Standard User (member of Power
Users group) and will run as a Restricted User (member of Users Group)
although will show errors when trying to update the registry.
To avoid these errors specific registry access can be provided by an
Administrator to the following registry keys:
•
HKEY_CLASSES_ROOT\CLSID\{0002D780-0000-0000-C000-
000000000046}
•
HKEY_CLASSES_ROOT\CLSID\{0002D781-0000-0000-C000-
000000000046}
•
HKEY_CLASSES_ROOT\CX-Supervisor.Application
•
HKEY_CLASSES_ROOT\CX-Supervisor.Project
•
Can I use CX-Simulator with CX-Supervisor?
Integrated Simulation can be used to automatically launch and use CX-
Simulator. See 'Compiling and Running a Project' for more details.
Omron's CX-Simulator virtual PLC can also be manually configured for
use with CX-Supervisor. To achieve this follow these steps:
1.Start CX-Simulator from the windows Start menu.
2.Select 'Create New PLC'
3.Select the required PLC Type
4.No need to register I/O ---> Next
5.Keep default Virtual Comms Unit ---> Next
6.Keep default Comm Port ---> Next