Wiring; Relay Status Connections; Table 3: Dip Switch Selection - Wheelock POWERPATH PS-12/24-8CP Installation Instructions Manual

Power booster
Hide thumbs Also See for POWERPATH PS-12/24-8CP:
Table of Contents

Advertisement

2.3 WIRING

Review the Operation Section (3.0) in order to select the proper hook-up and use of the POWERPATH.
Set switches and wire the POWERPATH as follows: Terminal locations are shown in Figure 1.
Set Power Supply switch (SW1) for 120VAC or 240VAC operation. See Figure 1.
A.
Set Power Supply switch (SW4) for desired output voltage (Down for 24VDC, Up for 12VDC). See
Figure 1.
B.
Set output DIP Switch(s) to follow corresponding input (IN1, IN2) and desired output mode. See Table
3 DIP Switch Selection and DIP Switch Settings Section (3.2).
C. Set DIP Switch SW9 position 1 & 2 to select Class "A" or Class "B" operation (Off for Class "B", On for
Class "A"). See Figure 1.
D. Dress battery wire down to the back of the enclosure, observing ¼" separation of power limited wire
V.S. non-power limited wiring. See Figure 3.
E. Connect notification appliances to desired outputs OUT1 – OUT4. See Operation Section (3.0).
The POWERPATH has in-out wiring terminals that accept two #18 to #12 American Wire Gauge (AWG) wires
at each screw terminal. Strip leads 3/8 inches and connect to screw terminals.
Separate all in-out wire runs on supervised circuits to insure integrity of circuit supervision. The polarity shown
in the wiring diagrams and on the circuit boards is for operation of the appliances. The polarity is reversed by
the FACP during supervision.
Total load for the PS-12/24-8CP NAC circuits shall not exceed 8.0 Amps.
Total load of any Class "B"output circuit shall not exceed 3.0 Amps.
Total load of any Class "A"output circuit shall not exceed 3.0 Amps.
Terminate unused outputs with a 2.2K Ohm EOLR.
F.
Connect the indicating circuit(s) from the FACP to the desired input(s), IN1 and IN2. Connect EOLR to
RET1 and RET2. The value is determined by FACP.
G. Connect desired auxiliary equipment to the auxiliary output terminals +AUX-.
Total load of the AUX output shall not exceed 0.06 Amps during 60 hour battery backup. This is UL listed for
5 minute of alarm power. See BATTERY CALCULATION SHEET for further information.
Total load of the AUX output shall not exceed 0.2 Amps during 24 hour battery backup.
H.
Connect trouble relays as desired.
I.
Connect backup batteries. Observe correct polarity and voltage. For 12VDC, use a single 12V battery.
For 24VDC, use two of the same connected in series. Use either a 7AH or a 12AH battery depending
on circuit loading, BATTERY CALCULATION SHEET is provided on Sheet 22.
J. Install battery cover between both battery wires and Power Limited Wiring. See Figure 3.
K. Connect AC source. The AC source shall be connected to a dedicated, non-switch power source. The
AC must first be wired into the buildings main electrical power. The conduit entry can be either from the
top or left hand side using the knock-outs. See Figure 3. Connect Earth Ground First.
L. Press Auxiliary Power Reset, SW7 to ensure that Auxiliary Power is present.
M. Close door and secure with 2 screws on side.
Function
INPUT
SELECT
TEMPORAL
IN>OUT SYNC
WHEELOCK
WHEELOCK SYNC "ON"
SYNC MODE
IN>OUT SYNC "ON"
NOTE 1: Use only with appliances that can operate using a coded horn appliance. (Example: Wheelock Series CH, and
Series MT)
NOTE 2: Use only with Wheelock Series AS/AH, Series NS/NS4/NH, Series RSS and products with SL/SLM strobes.

2.4 RELAY STATUS CONNECTIONS

COMMON TROUBLE TERMINALS – The common trouble terminals are located on the right bottom side of the PC
Board. The three terminals are labeled "NO", "C" and "NC". When the PS-12/24-8CP is operating normally the "NC" "C"
terminals are shorted, and the "C" "NO" terminals are open. There are five trouble conditions that will cause these
terminals to change state. The relay follows the trouble condition and is not latching.
Supervision trouble on any output
(+OUT1-, +OUT2-, +OUT3-, +OUT4-)
AC Loss
Micro Processor Fault
P84515 E

Table 3: DIP Switch Selection

Switch Position
ON
Selected output to be controlled by Input 1 (IN1+, IN1-) (DRY1)
OFF
Selected output to be controlled by Input 2 (IN2+, IN2-) (DRY2)
ON
Generates Code 3 temporal signal on this output.
ON
Allows a sync signal on the input to be used by the output.
Generates Wheelock sync signal for synchronizing Wheelock horns
and strobes.
Description
Battery Fail
GND Fault
Note
------
------
1
------
2
Sheet 9 of 23

Advertisement

Table of Contents
loading

Table of Contents