Wheelock POWERPATH PS-12/24-8CP Installation Instructions Manual page 18

Power booster
Hide thumbs Also See for POWERPATH PS-12/24-8CP:
Table of Contents

Advertisement

Example 13: WHEELOCK SYNC MODE without Audible Silence (CLASS A)
F
A
C
P
This mode will only synchronize Wheelock horns, horn strobes, and strobes with the synchronization capability.
If only strobes are connected to the POWERPATH outputs, the initiating input to IN2 is not required.
When synchronized horns are used on the two wire output of the POWERPATH, IN2 must be connected as
shown or the horns will not operate.
Example 14: WHEELOCK SYNC MODE with Audible Silence (CLASS A)
F
A
C
P
This mode will only synchronize Wheelock horns, horn strobes, and strobes with the synchronization capability.
COMBINATION CLASS "A" AND CLASS "B" HOOKUP
The PS-12/24-8CP POWERPATH can be configured to have one Class "A" (3.0 Amps) and two Class "B" (2.0 Amps
each circuit) Outputs at the same time. This is done by Switch SW9 position 1 & 2. NOTE: When SW9 position 1 is
on, OUTPUTS 1 and 3 are the Class "A" circuit. When SW9 position 2 is on, OUTPUTS 2 and 4 are the Class "A"
circuit.
COMBINATION OF MODES
In Class "B" configuration, each output can be set to an independent mode as desired.
In Class "B", IN1 or IN2 can be selected to activate any of the outputs desired.
In Class "A", OUTPUT DIP Switches must be set identically for each Class "A" output.
P84515 E
+
IN1
-
ON
-
RET1
+
POWERPATH
+
IN2
-
TO NEXT APPLIANCE
-
OR EOLR
RET2
OR RETURN
+
TO FACP
SW9
(CLASS "A")
+
IN1
-
TO NEXT APPLIANCE
+
OR EOLR
RET1
ON
OR RETURN
-
TO FACP
(CLASS "A")
POWERPATH
AUDIBLE SILENCE
+
IN2
-
TO NEXT APPLIANCE
+
OR EOLR
RET2
OR RETURN
-
SW9
TO FACP
(CLASS "A")
OUT1-4
+
IN>OUT SYNC
OUT1
-
WHEELOCK SYNC
TEMPORAL
INPUT SELECT
+
OUT2
-
-
OUT3
+
-
OUT4
+
OUT1-4
IN>OUT SYNC
+
OUT1
WHEELOCK SYNC
-
TEMPORAL
INPUT SELECT
+
OUT2
-
-
OUT3
+
-
OUT4
+
Sheet 18 of 23