Example 9: TEMPORAL MODE (CLASS A)
F
A
C
P
CAUTION: Strobes require constant voltage and will not operate properly in the TEMPORAL MODE. A second
Class "A" output set in the NORMAL MODE will provide the constant voltage for the strobe circuit. Only use sounding
appliances that can use a coded signal. Do not use Wheelock AS/AH or NS/NS4/NH appliances with TEMPORAL
MODE.
Example 10: IN>OUT SYNC MODE from CODED INPUT SOURCE (CLASS A)
F
A
C
P
CAUTION: Strobes require constant voltage and will not operate properly in the IN>OUT SYNC MODE with a
coded input. A second Class "A" output set in the NORMAL MODE will provide the constant voltage for the strobe
circuit. Only use audible appliances that can use a coded signal. Do not use Wheelock AS/AH or NS/NS4/NH
appliances with a coded input.
P84515 E
+
IN1
-
TO NEXT APPLIANCE
ON
+
OR EOLR
RET1
OR RETURN
-
TO FACP
(CLASS "A")
ON
POWERPATH
SW9
CODED
+
IN1
-
TO NEXT APPLIANCE
ON
+
OR EOLR
RET1
OR RETURN
-
TO FACP
(CLASS "A")
ON
CONSTANT
+
IN2
-
POWERPATH
TO NEXT APPLIANCE
+
OR EOLR
RET2
OR RETURN
-
SW9
TO FACP
(CLASS "A")
OUT3
OUT1
IN>OUT SYNC
OUT1
WHEELOCK SYNC
TEMPORAL
INPUT SELECT
ON
OUT2
OUT4
IN>OUT SYNC
OUT2
WHEELOCK SYNC
TEMPORAL
INPUT SELECT
ON
OUT3
OUT4
OUT3
OUT1
OUT1
IN>OUT SYNC
WHEELOCK SYNC
TEMPORAL
INPUT SELECT
ON
OUT2
OUT4
OUT2
IN>OUT SYNC
WHEELOCK SYNC
TEMPORAL
INPUT SELECT
ON
OUT3
OUT4
+
-
+
-
-
+
-
+
+
-
+
-
-
+
-
+
Sheet 16 of 23