3.0 OPERATION:

3.1 MODES OF OPERATION

The PS-12/24-8CP POWERPATH can provide a 12VDC or 24VDC output when initiated by a 8VDC to
33VDC appliance (IN1 or IN2) or an open contact (DRY1 or DRY2). The output will remain on until the
deactivation of the input returns it to standby mode.
The outputs can be configured as four Class "B" circuits, two Class "A" circuits, or two Class "B" and one
Class "A" circuits.
Each Class "A" circuit is 3.0 Amps and each Class "B" circuit is 3.0 Amps. Total load for the PS-12/24-8CP
NAC circuits shall not exceed 8.0 Amps.
There are four output modes which can be used with either Class "A" or Class "B" circuits.
NORMAL MODE
TEMPORAL MODE
IN>OUT SYNC MODE
WHEELOCK SYNC MODE

3.2 DIP SWITCH SETTINGS

The following is the DIP Switch settings for Output 1. Each of the remaining outputs is controlled similarly.
When switches are changed, press SYS RESET and wait 30 seconds before activating.
2
MODE
NORMAL MODE
TEMPORAL
IN>OUT SYNC
WHEELOCK SYNC
P84515 E
Used for a constant 12VDC or 24VDC output.
Provides a temporal output for appliances that can utilize a coded
signal. (i.e. single stroke bells and chimes and some horns) (NOTE:
Do not use with Wheelock AS, NS, RSS appliances.)
Allows a coded signal or synchronization signal input to be utilized by
the POWERPATH. This signal may come from a FACP, another PS-
12/24-8CP or a Wheelock Synchronization Module (SM-12/24 or DSM-
12/24). Audibles can also be silenced.
Activates the built-in Wheelock Synchronization Mode for use with
patented synchronized horns and strobes.
silenced.
Figure 4:
Output DIP Switch(s)
ON
DIP SWITCH
INPUT SELECT (1)
TEMPORAL (2)
WHEELOCK SYNC (3)
IN>OUT SYNC (4)
INPUT SELECT (1)
TEMPORAL (2)
WHEELOCK SYNC (3)
IN>OUT SYNC (4)
INPUT SELECT (1)
TEMPORAL (2)
WHEELOCK SYNC (3)
IN>OUT SYNC (4)
INPUT SELECT (1)
TEMPORAL (2)
WHEELOCK SYNC (3)
IN>OUT SYNC (4)
OUT1-4
IN>OUT SYNC
WHEELOCK SYNC
TEMPORAL
INPUT SELECT
SETTING
"ON"
for "IN1" or "DRY1"
"OFF" for "IN2" or "DRY2"
"OFF"
"OFF"
"OFF"
"ON"
for "IN1" or "DRY1"
"OFF" for "IN2" or "DRY2"
"ON"
"OFF"
"OFF"
"ON"
for "IN1" or "DRY1"
"OFF" for "IN2" or "DRY2"
"OFF"
"OFF"
"ON"
"ON"
for "IN1" or "DRY1"
"OFF" for "IN2" or "DRY2"
"OFF"
"ON"
"ON"
Audibles can also be
Sheet 11 of 23