Wheelock POWERPATH PS-12/24-8CP Installation Instructions Manual page 13

Power booster
Hide thumbs Also See for POWERPATH PS-12/24-8CP:
Table of Contents

Advertisement

Example 3:
IN>OUT SYNC MODE from CODED INPUT SOURCE (CLASS B)
F
A
C
P
Minimum pulse duration for coded signals must be greater than 0.4 seconds.
CAUTION: Strobes require constant voltage and will not operate properly in the IN>OUT SYNC MODE with a
coded input source. A second constant input with a second output set in the NORMAL MODE will provide the
constant voltage.
CAUTION: Only use audible appliances that can use a coded signal. Do not use with Wheelock Series AS/AH,
NS/NH or HS4/HS appliances.
Example 4:
IN>OUT SYNC MODE with External Sync Module without Audible Silence
(CLASS B)
SM/DSM
+ OUT1
F
+ IN1
MINUS 1
A
+ AUDIBLE
C
- AUDIBLE
P
NOTE:
When using the Wheelock external Sync Module (SM or DSM), synchronization will only occur with
Wheelock sync appliances.
P84515 E
CODED
+
IN1
-
TO NEXT APPLIANCE
+
OR EOLR
ON
RET2
-
CONSTANT
+
IN2
ON
-
POWERPATH
TO NEXT APPLIANCE
+
OR EOLR
RET2
-
SW9
TO NEXT APPLIANCE
OR EOLR
+
OUT1
OUT1
IN>OUT SYNC
WHEELOCK SYNC
TEMPORAL
-
INPUT SELECT
OUT2-4
+
IN>OUT SYNC
WHEELOCK SYNC
TEMPORAL
OUT2
INPUT SELECT
-
EOLR
+
OUT3
2.2K OHMS
-
EOLR
+
OUT4
2.2K OHMS
-
+
IN1
OUT1-4
-
IN>OUT SYNC
WHEELOCK SYNC
TEMPORAL
INPUT SELECT
ON
+
RET1
-
OUT2
POWERPATH
OUT3
SW9
OUT4
TO NEXT APPLIANCE
OR EOLR
(2.2K OHMS)
SW9
TO NEXT APPLIANCE
OR EOLR
(2.2K OHMS)
+
OUT1
-
EOLR
+
2.2K OHMS
-
EOLR
+
2.2K OHMS
-
EOLR
+
2.2K OHMS
-
Sheet 13 of 23
TO NEXT
APPLIANCE
OR EOLR
(2.2K OHMS)