1.5 LED STATUS

Table 2 lists status of the LED indicators. The ALARM condition occurs when the input causes the output circuits to energize.
TROUBLE condition occurs when the circuit is no longer supervised correctly. NOTE: An alarm condition overrides a trouble
condition.

1.6 BATTERY MAINTENANCE

Battery Replacement: Power-Sonic (or equal) 12VDC, replace with new batteries every four (4) years or as needed if battery will
no longer accept full charge. Two 12V batteries are required for 24VDC setting. Use either a 7AH battery for 5 minutes of alarm
or a 12AH battery for 15 minutes of alarm.
NOTE: Battery compartment measures 4-1/2" High X 11-1/2" Wide X 4-1/2" Deep.

2.0 INSTALLATION INSTRUCTIONS

NOTE: The PS-12/24-8 POWERPATH shall be installed in accordance with the National Electrical Code (NEC) and all
applicable state and local regulations.

2.1 UNPACKING

The POWERPATH was carefully checked before leaving the factory. Inspect shipping container and unit carefully for
indications of improper handling. If damage is detected, make an immediate claim to the carrier.
Remove the POWERPATH from the shipping container and check that the door lock keys, door lock, and battery connection
wires are inside. Make sure the transformer, Power Board and Logic Board are securely mounted to the rear of the enclosure.

2.2 MOUNTING

WARNING: TO REDUCE THE RISK OF FIRE OR ELECTRIC SHOCK, DO NOT EXPOSE THIS UNIT TO RAIN
OR MOISTURE.
CAUTION: This product is not intended for use in hazardous locations as defined by the National Electrical Code (NEC) and
by the National Fire Protection Association (NFPA).
Mount the POWERPATH in the desired location using the mounting dimensions in Figure 3.
Mount the panel in a location that does not exceed a temperature range of 0° C to 49° C (32° F to 120° F) and a humidity equal to
10% to 85% at 30° C (86° F) non-condensing.
When mounting on interior walls, use proper screw anchors in plaster. When mounting to concrete, especially when moisture is
expected, first attach a piece of ¾ inch plywood to the concrete surface. Attach the POWERPATH to the plywood.
CAUTION: The POWERPATH panel shall be mounted in a location within the environmental limits specified in the latest
UL Standard for indoor control panels.
P83862 M

Table 2: LED Status Description

LED
Logic Board
OUT1
OUT2
OUT3
OUT4
INP1
INP2
FAULT
Power Supply Board
AC
DC
OFF
ON
STANDBY
ALARM
STANDBY
ALARM
STANDBY
ALARM
STANDBY
ALARM
STANDBY
ALARM
STANDBY
ALARM
--------
TROUBLE
--------
--------
No AC
AC Present
No DC
DC Present
Blinking
TROUBLE
TROUBLE
TROUBLE
TROUBLE
TROUBLE
TROUBLE
--------
--------
--------
--------
Sheet 7 of 23