Class "A" Operation - Wheelock POWERPATH PS-12-24-8 Installation Instructions Manual

Power booster
Table of Contents

Advertisement

Example 7: WHEELOCK SYNC MODE with Audible Silence (CLASS B)
F
A
C
P
This mode will only synchronize Wheelock horns, horn strobes, and strobes with the synchronization capability.

3.4 CLASS "A" OPERATION

Class "A" circuit 1 uses "OUT1" and "OUT3". Class "A" circuit 2 uses "OUT2" and "OUT4". When operating in Class "A" the
two circuits must have the same switch settings for the operational mode selected. Switches SW1 and SW2 on the logic board are
in the "CLOSED" position.
IN1 and/or IN2 can be used for connection to the FACP. The INPUT SELECT Switch (4) selects which input is to be used
to activate the output.
Logic Board switches SW1 and SW2 control Class "A" or Class "B" configuration. SW1 controls Outputs 1 and 3. SW2
controls Outputs 2 and 4.
DIP Switch settings for each circuit in the Class "A" output must be set identically.
Example 8: NORMAL MODE (CLASS A)
F
A
C
P
P83862 M
+
OUT1-4
IN1
INPUT SELECT
-
TEMPORAL
STROBE SYNC
IN>OUT SYNC
TO NEXT APPLIANCE
O N
+
OR EOLR
RET1
-
POWERPATH
AUDIBLE
SILENCE
+
IN2
-
TO NEXT APPLIANCE
+
OR EOLR
RET2
-
LOGIC BOARD
SWI "OPEN"
SW2 "OPEN"
+
IN1
-
TO NEXT APPLIANCE
+
OR EOLR
RET1
-
OR RETURN
TO FACP
(CLASS "A")
POWERPATH
LOGIC BOARD
SWI "CLOSED"
SW2 "CLOSED"
+
OUT1
-
EOLR
+
OUT2
2.2K OHMS
-
EOLR
+
OUT3
2.2K OHMS
-
EOLR
+
OUT4
2.2K OHMS
-
OUT1-4
OUT1
INPUT SELECT
TEMPORAL
STROBE SYNC
IN>OUT SYNC
ON
OUT2
OUT3
OUT4
TO NEXT APPLIANCE
OR EOLR
(2.2K OHMS)
+
-
+
-
-
+
-
+
Sheet 15 of 23

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents