1.2 SPECIFICATIONS

Approvals:
UL Listed 864 Control for use with Fire Protective Signaling
MEA approved – NYC Dept. of Buildings
California State Fire Marshall (CSFM) approved
NFPA 72 compliant
Inputs:
115VAC, 60Hz, 3.2 AMP Operating Power in Alarm
12/24VDC Battery Backup Connection
Two (2), 12 or 24VDC NAC Initiating Circuits (9-30VDC at 5mA)
Two (2) "Dry" Contact initiating Circuits
Accepts two Class "A" or two Class "B" circuit inputs
Built in battery charger for sealed lead acid or gel type batteries
Outputs:
Switch selectable 12VDC or 24VDC power limited outputs
8 AMP continuous supply current at 12VDC or 24VDC for 5 minutes with 7AH battery or 15 minutes with 12AH
battery.
Capable of four (4), Class "B" circuits (2 Amps each)
Two outputs may be paralleled for a maximum output of 4 AMPS on a circuit (Class "B" only)
Capable of two (2) Class "A" circuits (2 Amps each).
Capable of one (1) Class "A" circuit (2 Amps) and two (2) Class "B" circuits (2 Amps each)
Code 3 or constant voltage output generation
Built-in Wheelock synchronization mode that can be fed to any or all of the output circuits
Input and output can be synchronized with "IN>OUT SYNC" mode (SM, DSM or 2
Audible silence capability
Filtered and electronically regulated output
50mA auxiliary output with reset capability
Supervision:
Compatible with 12 or 24VDC FACP
Signaling appliance loops are supervised and steered to either IN1 or IN2
22K OHM, ¼ Watt End-of-Line-Resistor (EOLR) for supervision of all outputs
Common input and output trouble circuits
Automatic switchover to standby battery when AC fails
Thermal and short circuit protection with auto reset
Input and output status LED indicators
AC fail supervision (Form "C" contact, 1 AMP 28VDC)
Battery presence and low battery supervision (Form "C" contact, 1 AMP 28VDC)
Auxiliary output fail supervision (Form "C" contact, 1 AMP 28VDC)
Ground Fault Detection (factory installed UL Listed 22K OHM resistor /wire assembly connected from positive (+)
AUX to chassis ground)

1.3 TERMINOLOGY

CLASS "A" = STYLE Z
CLASS "B" = STYLE Y
FACP = Fire Alarm Control Panel
EOLR = End-of-Line Resistor
NAC = Notification Appliance Circuit
SM = Wheelock Sync Module with single output.
DSM = Wheelock Sync Module with two outputs.
C = Common
NC = Normally Closed
NO = Normally Open
AH = Ampere/Hour