Download Print this page

Wheelock RPS-2440-A Installation Instructions

Regulated and filtered power supply ("a" battery)

Advertisement

Quick Links

273 Branchport Avenue
Long Branch, NJ 07740
(800) 631-2148
www.wheelockinc.com
Use this product according to this instruction manual. Please keep this instruction manual for future reference.
MODEL NO.: RPS-2440-A
DESCRIPTION: The RPS-2440-A Dual Power Supply consists of two "A" Battery outputs, each providing 2 Amps of current at
24VDC. When the two outputs are connected in parallel, the RPS-2440-A will provide up to 4 Amps of "A Battery current at 24VDC
fully regulated and filtered, each output is provided with independent LED "power" on indicators; current limiting, overload and short
circuit protection; automatic shutdown and reset.
NOTE: All CAUTIONS and WARNINGS are identified by the symbol
SPECIFICATIONS:
INSTALLATION: The RPS-2440-A is designed for shelf or wall mounting.
CAUTION: Make sure the power supply switch is in the "OFF" position, and the power line cord is not plugged in.
1)
Using the mounting screws provided, mount the Power Supply to a secure wooden surface. For other surfaces, appropriate
mounting hardware should be used See Figure 1.
2)
Remove terminal block cover by squeezing the clips at each end. See Figure 1A.
3)
Each of the Power Supply outputs provides 2 Amps. This allows 24VDC (to power the Paging System) to be conveniently
distributed over 2 independent 2 Amp circuits. See Figure 2. Alternately, the 2 outputs can be connected in parallel to provide
one 24VDC circuit providing up to 4 Amps. See Figure 3. Connect 24VDC to the Paging System, as specified on the individual
product instruction sheets. Snap cover back onto the terminal block clips.
4)
Plug in the Power Supply cord to a 117VAC outlet and push the power switch to the "ON" position. The 2 red "power" on LED's
(on the front panel will illuminate to indicate power is being supplied to each output. Each LED can be identified with its related
output by the designations A1 and A2.
Copyright 2001 Wheelock, Inc. All rights reserved.
Thank you for using our products.
INSTALLATION INSTRUCTIONS
REGULATED AND FILTERED
POWER SUPPLY ("A" BATTERY)
Nominal Output Voltage: 24VDC
Regulation: +/- 5%
Ripple Voltage: 10 mVrms maximum
Output Current:
(A) Each output: 2.0A
(B) Dual outputs: 4.0A
(connected in parallel)
Input Voltage: 117VAC, +/- 10%, 60Hz
Installation: 4 Binding Posts
Terminal Wire Gauge:
(A) Minimum: 24 (American Wire Gauge)
(B) Maximum: 14 (American Wire Gauge)
Note: For 12 AWG Wire, use Spade Lugs.
Duty Cycle: continuous
Power Line Cord: 6 Ft.
. All warnings are printed in bold capital letters.
P81642 G
Sheet 1 of 3

Advertisement

loading

Summary of Contents for Wheelock RPS-2440-A

  • Page 1 DESCRIPTION: The RPS-2440-A Dual Power Supply consists of two "A" Battery outputs, each providing 2 Amps of current at 24VDC. When the two outputs are connected in parallel, the RPS-2440-A will provide up to 4 Amps of "A Battery current at 24VDC fully regulated and filtered, each output is provided with independent LED "power"...
  • Page 2 4 Amps when the outputs are connected in parallel. If the problem is determined to be the power supply, return the unit to Wheelock for servicing. CAUTION: TO PREVENT ELECTRIC SHOCK DO NOT REMOVE COVER. NO USER SERVICEABLE PARTS INSIDE.
  • Page 3: Limited Warranty

    IN NO EVENT SHALL WHEELOCK BE LIABLE FOR ANY CLAIM OF ANY KIND UNLESS IT IS PROVEN THAT OUR PRODUCT WAS A DIRECT CAUSE OF SUCH CLAIM. FURTHER, IN NO EVENT, INCLUDING IN THE CASE OF A CLAIM OF NEGLIGENCE, SHALL WHEELOCK BE LIABLE FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES.