Master Remote Operation - Wheelock POWERPATH PS-12-24-8 Installation Instructions Manual

Power booster
Table of Contents

Advertisement

3.5 MASTER REMOTE OPERATION:

Example 15: Synchronized Multiple PS-12/24-8 Using a Master PS-12/24-8 (in the WHEELOCK SYNC
MODE) Without Audible Silence, and Using Input #1.
FACP
NAC Input in
Alarm Condition
NOTE 1
NOTE 1: NAC Input Voltage 9.0 to 30.0VDC Constant.
NOTE 2: OBSERVE DIP SWITCH SETTINGS
Input Selection Switch (Position 1) on OUT1 to OUT4 DIP Switches are shown in the "ON"
Position allowing Input #1 to activate Outputs 1-4, Positions 2-4 are set for "WHEELOCK SYNC MODE"
NOTE 3: Jumper "RET 1-" to "IN 2-" and "RET 1+" to "IN 2+ " only on the Master PS-12/24-8.
NOTE 4: Diagram shown with an output circuit (OUT4) on Master PowerPath used to synchronized the Remote PowerPaths. In
this configuration the Master PowerPath can only have three NAC circuits.
NOTE 5: Jumpers must be placed across "DRY 1" and "DRY 2" terminals when operating Power Supply using "IN 1" or "IN 2".
NOTE 6: OBSERVE DIP SWITCH SETTINGS
Input Selection Switch (Position 1) on OUT 1 to OUT 4 DIP Switches are shown in the "ON" Position allowing Input
#1 to activate Outputs 1-4. Positions 2-4 are set for "IN>OUT SYNC MODE".
P83862 M
_
+
AUX
NO "REMOTE" C
AUX
RESET
MASTER
-
+
SW2
SW1
_
_
+
+
OUT2
OUT1
NOTE 4
_
+
AUX
NO "REMOTE" C
AUX
RESET
REMOTE
SW2
SW1
_
_
+
+
OUT1
OUT2
_
+
AUX
NO "REMOTE" C
AUX
RESET
REMOTE
SW2
SW1
_
_
+
+
OUT1
OUT2
NOTE 2
_
DC
+
OUT1
OUT3
INPUT SELECT
TEMPORAL
STROBE SYNC
OUT1 OUT2 OUT3
IN>OUT SYNC
ON
ON
OUT2
OUT4
INPUT SELECT
TEMPORAL
STROBE SYNC
IN>OUT SYNC
ON
ON
ON OFF
ON OFF
INP1 INP2
JUMPERS
-
+
_
_
+
_
+
_
OUT3
OUT4
IN1
C "DRY1" NC
+
IN1
IN2
+
IN2
_
_
RET1
RET2
RET2
RET1
+
+
C "DRY2" NC
-
+
FACP
EOLR
NOTE 6
_
DC
+
OUT1
OUT3
INPUT SELECT
TEMPORAL
STROBE SYNC
OUT1 OUT2 OUT3
IN>OUT SYNC
ON
ON
OUT4
OUT2
INPUT SELECT
TEMPORAL
STROBE SYNC
IN>OUT SYNC
ON
ON
ON OFF
ON OFF
INP1 INP2
-
+
_
_
+
+
_
_
OUT3
OUT4
IN1
IN1
IN2
C "DRY1" NC
+
+
IN2
_
_
RET2
RET1
+
RET1
RET2
C "DRY2" NC
+
+
-
NOTE 6
_
DC
+
OUT1
OUT3
INPUT SELECT
TEMPORAL
STROBE SYNC
OUT1 OUT2 OUT3
IN>OUT SYNC
ON
ON
OUT4
OUT2
INPUT SELECT
TEMPORAL
STROBE SYNC
IN>OUT SYNC
ON
ON
ON OFF
ON OFF
INP1 INP2
+
-
_
_
+
_
+
_
OUT4
C "DRY1" NC
OUT3
IN1
+
IN1
IN2
+
IN2
_
_
RET2
RET2
RET1
+
RET1
+
C "DRY2" NC
ADDITIONAL PS-12/24-8
APPLIANCES OR
2.2K OHM EOLR
OUT4
FAULT
NOTE 3
NOTE 5
UPPER
LOWER
OUT4
FAULT
NOTE 5
UPPER
LOWER
OUT4
FAULT
NOTE 5
UPPER
LOWER
Sheet 19 of 23