Wheelock POWERPATH PS-12-24-8 Installation Instructions Manual page 15

Power booster
Table of Contents

Advertisement

Example 5: IN>OUT SYNC MODE with External Sync Module with Audible Silence (CLASS B)
SM/DSM
+ OUT1
F
+ IN1
MINUS 1
A
+ AUDIBLE
EOLR
C
- AUDIBLE
P
NOTE: When using the Wheelock external Sync Module (SM or DSM), synchronization will only occur with Wheelock sync
appliances.
Example 6: WHEELOCK SYNC MODE without Audible Silence (CLASS B)
F
A
C
P
This mode will only synchronize Wheelock horns, horn strobes, and strobes with the synchronization capability.
If only strobes are connected to the POWERPATH outputs, the initiating input to IN2 is not required.
When synchronized horns are used on the two wire output of the POWERPATH, IN2 must be connected as shown or the
horns will not operate.
P83862 M
OUT1-4
INPUT SELECT
+
TEMPORAL
IN1
STROBE SYNC
-
IN>OUT SYNC
ON
TO NEXT
APPLIANCE
+
OR EOLR
RET1
-
POWERPATH
LOGIC BOARD
SWI "OPEN"
SW2 "OPEN"
OUT1-4
+
INPUT SELECT
IN1
-
TEMPORAL
STROBE SYNC
IN>OUT SYNC
-
ON
RET1
+
POWERPATH
+
IN2
-
+
TO NEXT APPLIANCE
RET2
-
OR EOLR
LOGIC BOARD
SWI "OPEN"
SW2 "OPEN"
+
OUT1
-
EOLR
+
OUT2
2.2K OHMS
-
EOLR
+
OUT3
2.2K OHMS
-
EOLR
+
OUT4
2.2K OHMS
-
+
OUT1
-
EOLR
+
OUT2
2.2K OHMS
-
EOLR
+
OUT3
2.2K OHMS
-
EOLR
+
OUT4
2.2K OHMS
-
TO NEXT APPLIANCE
OR EOLR
(2.2K OHMS)
TO NEXT APPLIANCE
OR EOLR
(2.2K OHMS)
Sheet 14 of 23