Siemens 38-3AH3 38 kV Instruction Manual page 65

Vacuum circuit breaker
Table of Contents

Advertisement

General
Rated
Rated
values
voltage
Insulation
levels
Rated
current
Related
Current
required
capabilities
Closing and
latching
(momentary)
These ratings are in accordance with:
ANSI/IEEE C37.04-1979 Standard Rating
Structure for AC High-Voltage Circuit
Breakers Rated on a Symmetrical
Current Basis
ANSI C37.06-1987 AC High-Voltage
Circuit Breakers Rated on a Symmetrical
Current Basis - Preferred Ratings and
Related Required Capabilities
ANSI/IEEE C37.09-1979 Standard Test
Procedure for AC High-Voltage Circuit
Breakers Rated on a Symmetrical
Current Basis
ANSI/IEEE C37.010-1979 Application
Guide for AC High-Voltage Circuit
Breakers Rated on a Symmetrical
Current Basis.
Appendix
Table 13: Type 38-3AH3 vacuum circuit breaker ratings (historic "constant MVA" ratings basis)
Measured parameter
Nominal voltage class
Nominal three-phase MVA class
Maximum design voltage (V)
Voltage range factor (K)
Withstand
voltage levels
Lightning-impulse (BIL)
Continuous
Short-circuit (at rated maximum design voltage) (I)
Interrupting time
Permissible tripping delay (Y)
Rated maximum design voltage (V) divided by K = (V/K)
Maximum symmetrical (sym) interrupting (K x I)
Short-time current (K x I) (three-seconds)
Asymmetrical (1.55 x I)
Peak (2.6 x I)
Footnotes:
"xxxx" in type designation refers to the
1
continuous current rating 1,200, 2,000, or
3,000 A, as appropriate. The 3,000A fan-cooled
rating is achieved using fan cooling as
indicated in Footnote 4.
Maximum design voltage the circuit breaker is
2
designed for and the upper limit for operation.
K is the ratio of the rated maximum design
3
voltage to the lower limit of the range of
operating voltage in which the required
symmetrical and asymmetrical interrupting
capabilities vary in inverse proportion to the
operating voltage.
4
3000FC indicates fan cooling is included in the
switchgear structure for this rating. 3000 A
rating is not available in outdoor equipment.
To obtain the required symmetrical
5
interrupting capability of a circuit breaker at an
operating voltage between 1/K times rated
maximum design voltage and rated maximum
design voltage, the following formula shall be
used: Required Symmetrical Interrupting
Capability =Rated Short-Circuit Current (I) x
[(Rated Maximum Design Voltage)/(Operating
voltage)].
9
2
3
Power-frequency
4
5, 6, 10
11
8
8
Units
Circuit breaker type
38-3AH3-1500
kV
MVA
kV rms
----
kV rms
kV peak
A rms
1,200, 2,000, 3,000FC
kA rms sym
Cycles/ms
Sec
kA rms
kA rms sym
kA rms sym
kA rms
kA peak
For operating voltages below 1/K times
maximum design voltage, the required
symmetrical interrupting capability of the
circuit breaker shall be equal to K times rated
short-circuit current.
Within the limitations stated in ANSI/IEEE
6
C37.04-1979, all values apply to polyphase and
line-to-line faults. For single phase-to-ground
faults, the specific conditions stated in clause
5.10.2.3 of ANSI/IEEE C37.04-1979.
Current values in this row are not to be
7
exceeded even for operating voltage below 1/K
times rated maximum design voltage. For
operating voltages between rated maximum
design voltage and 1/K times rated maximum
design voltage, follow Footnote 5.
Current values in this row are independent of
8
operating voltage up to and including rated
maximum voltage.
"Nominal three-phase MVA class" is included
9
for reference only. This information is not listed
in ANSI/IEEE C37.06-1987.
Standard duty cycle is CO - 15s - CO.
10
Three-cycle (50 ms) interrupting is optionally
11
available.
1
38.0
1500
38.0
1.65
80
150
21
5/83
2
23.0
35
35
56
95
65

Advertisement

Table of Contents
loading

Table of Contents