Appendix D. Vendor Information

Appendix D.1. Connection to York Modbus Microgateway

If connecting the FieldServer to a York Modbus Microgateway, the Node_ID of the Microgateway is defined by the
address DIP switches. If switch 4 is set to 'On' and the other switches are set to 'off' then Node_ID of the
Microgateway is '247', the parity is 'Even', and the stop bits are 1. Other Node_ID combinations can be found in
the York Modbus Microgateway Installation Manual.

Appendix D.2. Modbus ASCII - Examples of FieldServer setup for typical clients

Appendix D.2.1.
FieldServer with GE Cimplicity as client
Run the Cimplicity "Workbench" and create a "New Project" with a unique "Project Name" option of
"Basic Control" and protocol "Modbus ASCII".
Check the project properties and continue with the "Project Wizard Setup" that appears.
Add Modbus port giving it a description.
Create and configure the devices, select "new item".
Name the device, select the port, give it a description (e.g. FieldServer), and choose "SYSTEM" resource.
Create and configure the points.
Select "new item", name the point and choose the appropriate device.
Under the "General" tab, point properties require a description. Note that the elements must have a
value greater than 8.
Under the "Device" tab, properties need the appropriate address (e.g. 40001 and also require the leading
0's), change the update criteria to "On Scan".
When the project is configured, run by pressing the "play" button.
Expect the Cimplicity driver to connect and poll the FieldServer for a range of valid addresses, and then
proceed to poll for just the configured Points.
From the start menu choose the "Point Control Panel", select edit and add the project you want to view.
Note, to log on the User name "ADMINISTRATOR" must be supplied
Use "Modbus ASCII Diagnostics" to connect to host and then read the register.
Appendix D.2.2.
FieldServer with Intellution FIX as a client
Install Intellution FIX, choosing the MB1 Modbus ASCII I/O driver
Run from Start menu and choose "Intellution Fix".
Choose "System Configuration Utility".
Modify SCADA, add the MB1 Modbus ASCII I/O driver
Configure the Modbus ASCII Driver.