Circuit Breaker and Fuse Sizes
The inverter's connections to input power for 400V class units must include
UL Listed inverse time circuit breakers with 600V rating, or UL Listed fuses
as shown in the table below.
Input
Voltage
Single/
Three-
Phase
200V
Three-
Phase
400V
Motor Overload Protection
Hitachi X200 inverters provide solid state motor overload protection, which
depends on the proper setting of the following parameters:
• B012 "electronic overload protection"
• B212 "electronic overload protection, 2nd motor"
Set the rated current [Amperes] of the motor(s) with the above parameters. The
setting range is 0.2 * rated current to 1.0 * rated current.
WARNING: When two or more motors are connected to the inverter, they
cannot be protected by the electronic overload protection. Install an external
thermal relay on each motor.
Inverter Model
X200-002SFFE/NFU
X200-004SFFE/NFU
X200-005SFFE
X200-007SFFE/NFU
X200-011SFFE
X200-015SFFE/NFU
X200-022SFFE/NFU
X200-037LFU
X200-055LFU
X200-075LFU
X200-004HFE/HFU
X200-007HFE/HFU
X200-015HFE/HFU
X200-022HFE/HFU
X200-030HFE
X200-040HFE/HFU
X200-055HFE/HFU
X200-075HFE/HFU
- 24 -
Circuit breaker /
Fuse
Inverse time circuit
breaker
Distribution Fuse
(Class J)
Ampere rating for
Fuse or Breaker
10
15
20
30
40
50
3
6
10
10
15
15
20
25